5. Pre-Installation

5.1 Material list

The unit is packed with following materials. Please confirm the series number on Energier pro bi-directional inverter is same to that on
outer carton.
Energier pro bi-directional inverter
TS – battery temperature sensor
VS – battery voltage sensor(optional)
User's manual

5.2 Location

Please install the equipment in a location of Dry, Clean, Cool with good ventilation.
Working temperature :-10℃-55℃
Storage temperature :-40-70℃
Relative Humidity
:0%-95%,non-condensing
Cooling
:Forced air

5.3 Wiring recommendation

Please find the following minimum wire size. In case of DC cable longer than 1m, please increase the cross section of cable to reduce the loss.
System capacity
CF08xx
CF12xx
CF16xx
CF20xx
CF30xx
CF40xx
CF50xx
CF60xx
CF80xx
AC wiring
110 VAC
230 VAC
2.5 mm²
2.5 mm²
4 mm²
2.5 mm²
4 mm²
2.5 mm²
4 mm²
2.5 mm²
/
4 mm²
/
4 mm²
/
6 mm²
/
10 mm²
/
10 mm²
DC wiring
12 VDC
24 VDC
16 mm²
10 mm²
25 mm²
16 mm²
35 mm²
25 mm²
50 mm²
25 mm²
70 mm²
50 mm²
/
/
70 mm²
/
/
29
Energier pro User Manual
48 VDC
/
/
/
16 mm²
25 mm²
/
25 mm²
50 mm²
/
50 mm²
/
70 mm²