8.Specification

Model No.
12VDC
24VDC
48VDC
INVERTER
Nominal Voltage
Cont. power @25℃( VA)
Cont. power @25℃( W)
Cont. power @40℃( W)
Output voltage
Output frequency
Cos φ
>110%
Overload
>125%
Capability
>150%
Overload
>150%
Capability(Bypass)
>200%
Surge
12 V
Efficiency (MAX.)
24 V
48 V
Crest factor
THD
UPS mode
Bypass range
GEN mode
Weak Grid
Zero load power
Zero load power
(power save mode)
Overload and
overheat protection
Shortcut protection
CF0825L CF1240L CF1645L CF2060L CF3090L
CF0815M CF1220M CF1625M CF2030M
/
/
/
12 VDC / 24 VDC
800
1200
1600
750
1100
1300
700
1000
1200
230 VAC / 110 VAC ± 2%
15 mins
184VAC-264 VAC / 88 VAC-127 VAC
173 VAC-276 VAC / 67 VAC-132 VAC
167 VAC-264 VAC / 80 VAC-127 VAC
10W / 11W 11W / 12W 11W /13 W
2.5W
2.5W / 3W 2.5W / 3 W
auto disconnect with 3 times restart attempt
/
CF3045M
/
CF2015S CF3020S
CF4030S
12 VDC / 24 VDC 48 VDC
2000
3000
4000
1600
2500
3500
1450
2200
3200
50 / 60 Hz ± 0.1%
0.9-1
60 s
20 s
60 s
Immediately
300%
89%
92%
95%
3:1
<3%
14W
17W
25W
3.5W
4W
6W
auto disconnect
44
Energier pro User Manual
/
/
CF5090M
/
/-TAI
CF5040S
CF6050S
CF8060S
/-TAI
/-TAI
/-TAI
5000
6000
8000
4500
5000
7000
4000
4500
6000
230 VAC± 2%
1 mins
184 VAC- 264VAC
173 VAC- 276 VAC
167 VAC- 264 VAC
26W
28W
6.5W
7W
7.5W
/
/
30W