9.3 Common failure analysis
Following please find frequent common failure which no maintenance on Energier pro bi-directional inverter was needed.
9.3.1 No output first power on
Phenomenon 1:No output at inverter mode, No alarm.
Reason :Battery low voltage.
Solution :Check battery voltage; Check battery capacity; Check battery LVD setting.
Phenomenon 2:No output at inverter mode, No alarm, Burn smell.
Reason :DC input reverse polarity.
Solution :Replace PCB.
9.3.2 No output during operation
Phenomenon 1:No output at inverter mode upon load switch on, fault and power saving mode lights illuminate.
Reason :Battery low voltage.
Solution :Check battery voltage; Check battery capacity; Check battery LVD setting.
Phenomenon 2:No output, long beep, fault and inverter lights illuminate.
Reason :Output shortcut .
Solution :Remove output shortcut.
Phenomenon 3:No output, fault and charging lights illuminate.
Reason :High DC voltage.
Solution :Check DC voltage .
Phenomenon 4:No output, fault and overload lights illuminate.
Reason :Overload shutdown.
Solution :Reducing load and switch on again.