2.18 Dry contact

Dry Contact Input
A group of dry contact input (Auxiliary In) was available on Energier pro bi-directional inverter, of which can be used to remotely
turn off the equipment.
Only Dry Contact.
Dry Contact Output
A group of dry contact output (Auxiliary Out) was available on Energier pro bi-directional inverter. The default setting of this dry contact
output was battery low voltage.It will activate once the voltage was detected dropping to preset level. This dry contact can be used for
load management or other function.
Through Vision Lite or Rapconfig, other functions can be configured for this contact.
The maximum contact load is:
230 VAC : 2 A
12 VDC / 24 VDC / 36 VDC : 2 A
Please find following chart the default setting:
LVD setting
10.5 VDC
11.7 VDC
Default
LVD setting
11 VDC
21 VDC
12 VDC
23.4 VDC
Default
LVD setting
22 VDC
42 VDC
24 VDC
46.8 VDC
11
Energier pro User Manual
Default
44 VDC
48 VDC