9.4 Set output signals
9.4.1 Set output functions
► Select [ou1] and set the switching function:
- [Hno] = hysteresis function/normally open
- [Hnc] = hysteresis function/normally closed
- [Fno] = window function/normally open
- [Fnc] = window function/normally closed,
- [OFF] = output off�
Parameter [OFF] is only available in operating mode 3 ([CMPT] = [3])�
► Select [ou2] and set the function:
- [Hno] = hysteresis function/normally open
- [Hnc] = hysteresis function/normally closed
- [Fno] = window function/normally open
- [Fnc] = window function/normally closed,
- [OFF] = output off�
Parameter [OFF] is only available in operating mode 3 ([CMPT] = [3])�
9.4.2 Define switching limits for the hysteresis function
► [ou1] / [ou2] must be set as [Hno] or [Hnc]�
► Select [SP1] / [SP2] and set the value at which the output switches�
► Select [rP1] / [rP2] and set the value at which the output switches off�
rPx is always smaller than SPx� The unit only accepts values which are lower
than the value for SPx�
9.4.3 Define switching limits for the hysteresis function
► [ou1] /[ou2] must be set as [Fno] or [Fnc]�
► Select [FH1] / [FH2] and set the upper limit value�
► Select [FL1] / [FL2] and set the lower limit value�
FLx is always lower than FHx� The unit only accepts values which are lower
than the value for FHx�