6 Electrical connection

The unit must be connected by a qualified electrician�
The national and international regulations for the installation of electrical
equipment must be adhered to�
Voltage supply according to EN 50178, SELV, PELV�
► Disconnect power�
► Connect the unit as follows:
Core colours
BK
black
BN
brown
BU
blue
WH
white
2: OUT2
4: OUT1
12
2
1
3
4
2 x pnp
1
BN
2
WH
4
BK
3
BU
OUT1: switching output or IO-Link
OUT2: switching output
Colours to DIN EN 60947-5-2
Example circuits
L +
2: OUT2
4: OUT1
L
BN
1
L +
2
WH
OUT2
4
BK
OUT1
3
BU
L
2 x npn
1
BN
2
WH
4
BK
3
BU
L +
L