Rccmd - Huawei RMS-SNMP01B User Manual

Snmp card
Table of Contents

Advertisement

RMS-SNMP01B SNMP Card
User Manual
Figure 4-34 Add NMS Address Info dialog box
Figure 4-35 Add SNMP TRAP

4.6.6 RCCMD

The UPS2000 SNMP card integrates the functions of the Generex RCCMD server:
ESN Configuration
For a single UPS, the ESN of the UPS is displayed on the Config > RCCMD > ESN
Configuration page by default, as shown in
Issue 10 (2020-03-20)
If you use Huawei NetEco, set Trap port to 162.
When the UPS generates an alarm, the SNMP card sends a shutdown command or
notification message to the RCCMD client.
The SNMP card configures and saves the address and port for receiving the shutdown
command, and the message sending mechanism.
Copyright © Huawei Technologies Co., Ltd.
4 Managing the UPS on the WebUI
Figure
4-36.
35