User Manual
Figure 4-20 RMS-RELAY02B Settings
Using DI1 and DO1 as examples, Table 4-4 and Table 4-5 list the association between DI/DO
status and UPS status.
Table 4-4 Association between DO status and UPS status
Name
DO1
DO1
Table 4-5 Association between DI status and UPS status
Name
DI1
DI1
DI1
DI1
Issue 10 (2020-03-20)
Associated
Event
Bypass mode
Bypass mode
Type
NO
NC
NO
NC
Copyright © Huawei Technologies Co., Ltd.
4 Managing the UPS on the WebUI
UPS Status
DO Status
Bypass mode
NO and COM pins of DO are
closed, NC and COM pins of DO
are open.
Mains mode
NC and COM pins of DO are
closed, NO and COM pins of DO
are open.
Associated
DI Status
Event
There is a
Startup
12–24 V DC
input.
Startup
There is a
12–24 V DC
input.
Startup
There is no
input.
Startup
There is no
input.
Execute Event
or Not
Yes
No
No
Yes
27