Appendix A. Instructions For High Altitude Installations (Us Only) - Crown Boiler AWR Series Installation Instructions Manual

Gas-fired natural draft hot water boilers
Table of Contents

Advertisement

Appendix A:
As with most gas appliances, special consideration must be given when this boiler is installed at altitudes
above 2000 ft:
AWR Series boilers is not certified for installation above 2000ft in Canada.
Do not install the AWR038B at altitudes above 2000ft anywhere.
When installed above 2000ft, input ratings for the AWR070B – AWR280B are derated by 4%
for each 1000 ft above sea level in accordance with The National Fuel Gas Code (NPA-54
ANSI Z223.1). For example, a boiler that is to be installed at 4000 ft must be derated by 16%.
This input derate is accomplished through the use of smaller main burner orifice. This reduc-
tion in input results in a correspondingly lower output and must be considered when sizing the
boiler. Approximate inputs as a function of altitude are shown in Table A1.
Safe operation of this boiler depends upon the use of the correct burner orifice. See the tables below for
the correct configuration. Failure to properly configure this boiler for the installation altitude could cause
personal injury or death due to Carbon Monoxide (CO) poisoning.
Orifice for this boiler cannot be drilled in the field. Obtain orifice for the proper altitude from the local
distributor (see Service Parts). Part Numbers for the correct size and style orifice are shown in Table A2.
Boilers that are factory configured for high altitudes have the altitude (or range of altitudes) for which the
boiler is configured marked on the packaging. Since it is possible for the orifice to be changed between the
factory and the end user, always verify that the correct orifice is in place for the installation altitude before
placing the boiler in operation. The size of the orifice may be found on one of its wrench flats.
Manifold pressures, as well as minimum and maximum inlet pressures, are the same as at sea level.
When orificing a boiler for an "odd" altitude, select the orifice for the higher altitude shown in the tables
below. For example, orifice a boiler being installed at 4100ft as though it were being installed at 5000ft.
When sizing a vent system for this boiler in accordance with the National Fuel Gas Code (NFPA-54/ANSI
Z223.1), use the sea level input ratings to determine the maximum capacity of a given vent system. Use
the high altitude input ratings in Table 1 to determine the minimum capacity of the vent system.
Model
Sea Level
AWR070
70000
AWR105
105000
AWR140
140000
AWR175
175000
AWR210
210000
AWR245
245000
AWR280
280000
* Based on the following Higher Heating Values: Natural Gas - 1020 BTU/scf, Propane - 2516 BTU/scf
Instructions for High Altitude Installations (US Only)
Table A1: Approximate Input (BTU/hr) at Various Altitudes*
2000
3000
64400
61600
58800
96600
92400
88200
128800
123200
117600
161000
154000
147000
193200
184800
176400
225400
215600
205800
257600
246400
235200
!
WARNING
!
CAUTION
Altitude (ft)
4000
5000
6000
56000
53200
84000
79800
112000
106400
140000
133000
168000
159600
196000
186200
224000
212800
54
7000
8000
9000
50400
47600
44800
75600
71400
67200
100800
95200
89600
126000
119000
112000
151200
142800
134400
176400
166600
156800
201600
190400
179200
10000
42000
63000
84000
105000
126000
147000
168000

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents