Crown Boiler AWR Series Installation Instructions Manual page 35

Gas-fired natural draft hot water boilers
Table of Contents

Advertisement

Parameter #
Description
Boiler Temperature
bt
Boiler water set point
SP
High Limit Set point
HL
High Limit Differential
HdF
Heat Request Status
tt
DHW Request Status
dh
Flame Current
FLA
Run Time Hours
run
CyC
Boiler Cycles
Error Number
Err
Status # Description
HL
dF
Or
PP
St
Pt
dh
rst
F-C
bAc
TABLE 11.4: OPERATING MODE PARAMETERS
Meaning
Current boiler water temperature measured by the control's sensor.
Current target temperature (always the same as the high limit setting.)
Boiler will stop firing if boiler water temperature exceeds this value (Circulator/s
will continue to operate)
If high limit setting is reached, boiler water temperature will need to drop by this
amount before boiler will again fire during the same call for heat.
Shown as either ON or OFF. Indicates whether there is a call for heat.
Shown as either ON or OFF. Indicates whether there is a call for domestic
hot water (DHW). Note that if the dh zone on the S9361A is used as a second
heating zone (see Table 11.5), this parameter will be shown as OFF and tt will be
shown as ON when this zone calls for heat.
Flame rectification signal (uA)
Total amount of time gas valve has been open (burner firing) since control was
new (hours, starting from 1).
Total number of burner cycles on the control
Present only if the control has detected a problem. See Table
error codes and suggested corrections.
TABLE 11.5: ADJUSTMENT MODE PARAMETERS
High Limit Set point
High Limit Differential
Circulator overrun
Thermal Purge time
Thermal Purge Start Temp
DHW Priority
Use of Second Zone
Reset
Temperature Units
Exit Adj. mode
Factory
Setting
Permissible Range
180F
140-220F
15F
10-30F
0 min
0-10 minutes
2 min
2-20 minutes
140F
140-180F
ON
ON or OFF
dh (dhw)
dh
or
tt2 (2nd heating zone).
OFF or
N/A
Momentary ON
F
F or C
N/A
N/A
35
13.0
for a list of