Page 1
These instructions must be affixed on or adjacent to the boiler Models: WARNING: Improper instal- lation, adjustment, alteration, BSI207 BSI069 • • service or maintenance can BSI241 BSI103 • cause property damage, injury, • or loss of life. For assistance or BSI276 BSI138 • • additional information, consult a...
Page 3
WARNINGS FOR THE HOMEOWNER FOLLOW ALL INSTRUCTIONS and warnings unless alarms or other safeguards are in place to printed in this manual and posted on the boiler. prevent such damage INSPECT THE BOILER ANNUALLY. To keep your DO NOT BLOCK AIR FLOW into or around the boiler safe and efficient, have a service technician boiler.
Table of Contents Product Description ............ 2 II. Specifications ............. 3 III. Before Installing ............4 IV. Locating the Boiler ............. 4 V. Air for Combustion & Ventilation ......5 VI. Venting ............... 9 VII. Gas Piping ..............12 VIII. System Piping............13 IX. Indirect Water Heater Piping ........16 X. Wiring ..............17 XI. Start-Up & Checkout ..........23 XII. Service & Maintenance ...........
III Before Installing 1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance with this manual and the requirements of the authority having jurisdiction. • In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the National Fuel Gas Code, ANSI Z223.1-latest edition. • Where required by the authority having jurisdiction, this installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1)-latest edition. Warning This Product Must be Installed By A Licensed Plumber Or Gas Fitter when Installed Within The Commonwealth Of Massachusetts 2) Make sure that a properly sized chimney is available which is in good condition. Consult the authority having jurisdiction, Part VI of this manual, and the National Fuel Gas Code for additional information on venting requirements.
FIGURE 2: BSI BOILERS - CLEARANCES TO ALL TYPES OF COMBUSTIBLE CONSTRUCTION AND NONCOMBUSTIBLE CEILINGS, WALLS, AND DOORS. • If the right side 24” service clearance is reduced, adequate clearance must be maintained to easily read and access the controls. Alternatively, access may be provided using a door 2) This boiler may be installed directly over a non-carpeted combustible floor. 3) The boiler must be installed on a hard level surface. 4) Do not install this boiler in a location where gasoline or other flammable vapors or liquids will be stored or used. Do not install this boiler in an area where large amounts of airborne dust will be present, such as a workshop. 5) The boiler should be located as close to the chimney as possible. 6) Do not install this boiler directly on a surface that may get wet. Raise the boiler on a pad. V Air for Combustion and Ventilation WARNING • INSUFFICIENT COMBUSTION AIR SUPPLY MAY RESULT IN THE PRODUCTION AND RELEASE OF DEADLY CARBON MONOXIDE (CO) INTO THE HOME WHCH CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.
Page 8
Sufficient fresh air must be supplied for combustion, ventilation and flue gas dilution. Provisions for combustion, ventilation and flue gas dilution air for gas utilization equipment vented by natural draft must be made in accordance with local building codes or, in absence of such codes, in accordance with sections 5.3.3 and 5.3.4 (“Air for Combustion and Ventilation”) of the National Fuel Gas Code, NFPA 54/ANSI Z223.1. To ensure an adequate supply of combustion, ventilation and flue gas dilution air supply, start by determining whether the boiler is to be installed in a building of unusually tight construction. A good definition of a building of unusually tight construction is one which has all of the following features: • Walls and ceilings exposed to outside atmosphere have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed • Weather stripping has been added on openable windows and doors • Caulking and sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings. For Buildings of Other than Unusually Tight Construction 1) Determine whether the boiler is to be installed in a confined space - A confined space is defined by the National Fuel Gas Code as having a volume less than 50 cubic feet per 1000 BTU/hr input of all appliances installed in that space. To determine whether the boiler room is a confined space: a. Total the input of all appliances in the boiler room in thousands of BTU/hr. Round the result to the next highest 1000 BTU/hr. b. Find the volume of the room in cubic feet. The volume of the room in cubic feet is: Length (ft) x width (ft) x ceiling height (ft) In calculating the volume of the boiler room, consider the volume of adjoining spaces only if no doors are installed between them. If doors are installed between the boiler room and an adjoining space, do not consider the volume of the adjoining space, even if the door is normally left open.
Page 9
FIGURE 3: BOILER INSTALLED IN CONFINED SPACE, ALL AIR FROM INSIDE FIGURE 4: ALL AIR FROM OUTDOORS, VENTILATED CRAWL SPACE AND ATTIC FIGURE 5: ALL AIR FROM OUTDOORS, VIA VENTILATED ATTIC...
Page 10
FIGURE 6: ALL AIR FROM OUTDOORS, USING OPENINGS INTO BOILER ROOM FIGURE 7: ALL AIR FROM OUTDOORS, USING HORIZONTAL DUCTS INTO BOILER ROOM...
For Buildings of Unusually Tight Construction 1) Openings must be installed between the boiler room and the outdoors or a ventilated space, such as an attic or crawl space, which communicates directly with the outdoors. 2) Two openings are required. The top edge of the upper opening must be within 12 inches of the ceiling. The bottom edge of the lower opening must be within 12 inches of the floor. 3) Size openings and ducts as follows: • Vertical ducts or openings directly outdoors (Figure 4, Figure 5, and Figure 6) - Each opening must have a free cross sectional area of 1 square inch per 4000 BTU/hr of the total input of all gas-fired appliances in the boiler room but not less than 100 square inches. Minimum opening size is 3 inches. • Openings to outdoors via horizontal ducts (Figure 7) - Each opening must have a free cross sectional area of 1 square inch per 2000 BTU/hr of the total input of all gas fired appliances in the boiler room but not less than 100 square inches. Minimum opening size is 3 inches. • The “free area” of an opening takes into account the blocking effect of mesh, grills, and louvers. Where screens are used, they must be no finer than ¼” (4 x 4) mesh. VI Venting WARNING • IMPROPER VENTING MAY RESULT IN PROPERTY DAMAGE AND/OR THE RELEASE OF FLUE GASES, WHICH CONTAIN DEADLY CARBON MONOXIDE (CO), INTO THE HOME, WHICH CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.
Page 12
3) Chimney and Vent Connector Sizing - Size the chimney and vent connector in accordance with the National Fuel Gas Code. 4) Exterior Chimneys - An exterior chimney has one or more sides exposed to the outdoors below the roof line. There are two conditions under which an exterior chimney may be used: • In some very restrictive cases, BSI series boilers may be vented into an exterior ceramic lined masonry chimney. See the National Fuel Gas Code for information on when exterior chimneys may be used. • An exterior masonry chimney may be used if it is lined with B vent or a listed chimney lining system. 5) This boiler may be vented using a listed power venter. The power venter must be sized and installed in accordance with the power venter manufacturer’s instructions, the terms of the power venter listing, and applicable codes. The boiler must be electrically interlocked with the power venter to prevent boiler operation if the power venter fails to operate. Before deciding to use a power venter, make certain that the flue gas exiting the power venter will not damage adjacent construction or other structures. Also make certain that the power venter terminal will not be subjected to winds which could effect power venter operation. 6) Do not connect the vent of this appliance into any portion of a mechanical vent system operating under positive pressure. 7) Do not connect the boiler into a chimney flue serving an open fireplace or other solid fuel appliance. 8) Prior to boiler installation, inspect chimney for obstructions or other defects and correct as required. Clean chimney as necessary. 9) Vent pipe should slope upward from draft diverter not less than one inch in four feet. No portion of vent pipe should run downward or have sags. Vent pipe must be securely supported. 10) The vertical section of vent pipe coming off the boiler should be as tall as possible, while still maintaining the proper clearance from the horizontal vent connector to combustibles and the proper pitch called for in (9) above. 11) Vent pipe should be installed above the bottom of the chimney to prevent blockage. 12) Vent pipe must be inserted flush with inside face of the chimney liner and the space between vent pipe and chimney sealed tight.
Page 13
FIGURE 8: BSI BOILER TYPICAL VENT SYSTEM INSTALLATION AND COMPONENTS RIGHT SIDE VIEW FIGURE 9: VENT DAMPER INSTALLATION DETAILS 11 11...
c) Insofar as practical, close all building doors and windows and all doors between the space in which all the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers. d) Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so the appliance will operate continuously. e) Test for spillage at the draft hood relief opening after five (5) minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe. f) After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliances to their previous condition of use. g) Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in the National Fuel Gas Code, ANSI Z223.1. VII Gas Piping WARNING • SHUT OFF GAS SUPPLY BEFORE SERVICING THE BOILER. • ALL GAS PIPING MUST BE GAS TIGHT. USE GAS RATED THREAD COMPOUND ON ALL THREADED JOINTS TO AVOID LEAKS, WHICH MAY RESULT IN FIRE OR EXPLOSION.
Gas piping to the boiler must be sized to deliver adequate gas for the boiler to fire at the nameplate input at a line pressure between the minimum and maximum values shown on the rating plate. For more information on gas line sizing, consult the utility or Chapter 2 of the National Fuel Gas Code. Figure 10 shows typical gas piping connection to the BSI boiler. A sediment trap must be installed upstream of all gas controls. Install a manual shut-off valve outside the jacket and ground joint union as shown. The boiler and its gas connection must be leak tested before placing the boiler in operation. When doing this, the boiler and its individual shut-off must be disconnected from the rest of the system during any pressure testing of that system at pressures in excess of 1/2 psi. When pressure testing the gas system at pressures of 1/2 psi or less, isolate the boiler from the gas supply system by closing its individual manual shut-off valve. VIII System Piping WARNING • INSTALL BOILER SO THAT THE GAS IGNITION SYSTEM COMPONENTS ARE PROTECTED FROM WATER (DRIPPING, SPRAYING, RAIN, ETC.) DURING APPLIANCE OPERATION AND SERVICE (CIRCULATOR REPLACEMENT, ETC.). •...
Page 16
• Hammering • Failure to heat one or more radiators Avoid the three common piping mistakes shown in Figure 12. This applies even if the existing boiler has one of the piping mistakes shown in Figure 12 and appears to be working. If two or more steam mains must be connected to the boiler, connect a separate take-off for each main into the header between the riser(s) and equalizer. Also note the following points: 1) A size reduction must be made to connect the header to the equalizer. This reduction must be made in the equalizer line. Do not make this size reduction in the horizontal header. 2) One pipe steam systems require air vents on each radiator, as well as at the end of each main. For the system to work properly, these vents must be properly installed, sized, and be in good condition. Inspect and replace any defective vents. If there are no vents at the ends of the mains, install them. 3) Do not attempt to manifold multiple BSIs with gravity returns. 4) For installations with condensate or boiler feed pumps, follow the pump manufacturer’s piping instructions. Such systems generally do not require Hartford loops. 5) Do not use a check valve in place of, or in addition to, a Hartford loop on a gravity return system. 6) Pipe the fill connection from a clean source of cold water. When the water supply is from a well, make sure that a strainer is installed in the well system. 7) Piping with a Chiller - If the boiler is used in conjunction with a chiller, pipe the boiler in parallel with chiller. Use isolation valves to prevent chilled water from entering the boiler. Piping Installation 1) Remove parts bag from boiler crate. 2) Install safety valve (spindle must be in vertical position) into tapping on boiler left side (see Figure 1) using the 3/4” NPT nipples and elbow supplied. 3) Pipe the discharge of the safety relief valve to a location where water or steam will not create a hazard or cause property damage if the valve opens. The end of the discharge pipe must terminate in an unthreaded pipe. If the safety valve discharge is not piped to a drain it must terminate at least 6 inches above the floor. The termination of the safety valve discharge piping must be in an area where it is not likely to become plugged by debris or subjected to freezing. 4) Install drain valve into tapping on boiler left side using the 2 x 3/4 bushing provided (see Figure 1). 5) Connect system supply and return to boiler. See Figure 11. The BSI069 - BSI172 require only one supply riser. Two supply risers are required on the BSI207 and larger sizes. 6) Piping with a Chiller - If the boiler is used in conjunction with a chiller, pipe the boiler in parallel with chiller. Use isolation valves to prevent chilled water from entering the boiler. 14 14...
IX Indirect Water Heater Piping All BSI series boilers are equipped with tappings to permit the connection of a Crown Mega-Stor, or other indirect water heater. In this type of system, hot boiler water is drawn from below the water line and passed through the heat exchanger in the indirect water heater. This section describes boiler-side piping only. Refer to the indirect water heater instruction manual for domestic water piping. The components in this system and their functions are as follows: 1) Circulator - Mount the circulator as shown in Figure 13. The circulator should be located as low and as close to the boiler as practical. Do not install valves, or other devices having a significant pressure drop, between the boiler and the circulator inlet. All piping between the boiler and the circulator inlet should be 1”, regardless of the size of the piping required in the rest of the system. See Figure 15 in Part X for wiring information. 2) “Y” Strainer - Install a “Y” strainer to prevent sediment from accumulating inside the indirect water heater. 3) Check Valve - Prevents gravity circulation through the indirect water heater when the boiler is responding to a call for heat. 4) Boiler Limit Control - Use a SPST break-on-rise temperature limit control such as the Honeywell L4006A. Do not set the limit above 180F as doing so may cause the boiler to steam when there is no call for heat. See Figure 15 for wiring information. 5) Valves and Unions - Install shut-off valves, drain valves, and unions in locations that will facilitate maintenance of the system. Do not install any valves between the boiler and circulator inlet. IMPORTANT • Some indirect water heaters may not be suitable for use with a steam boiler. Consult the water heater manufacturer’s guidelines before installing it in this type of system. • Boiler water temperatures and flow rates in this type of system may be considerably lower than those upon which the water heater manufacturer’s ratings are based. This may result in substantially longer water heater recovery times. FIGURE 13: INDIRECT WATER HEATER BOILER-SIDE PIPING 16 16...
X Wiring WARNING • ALL WIRING AND GROUNDING MUST BE DONE IN ACCORDANCE WITH THE AUTHORITY HAVING JURISDICTION OR, IN THE ABSENCE OF SUCH REQUIREMENTS, WITH THE NATIONAL ELECTRICAL CODE (ANSI/NFPA 70). • DISCONNECT ELECTRICAL POWER TO THE BOILER AND HEATING SYSTEM BEFORE SERVICING.
Page 20
• Connect the BLACK lead on the feeder to terminal A on the LWCO • Connect the WHITE lead on the feeder to terminal 2 on the LWCO 2) Using Hydrolevel VXT-24 THREE-WIRE feeder - Do not alter factory boiler wiring. Connect VXT-24 to CG400A as follows: • Connect the BLACK lead on the feeder to terminal 1 on the LWCO • Connect the WHITE lead on the feeder to terminal 2 on the LWCO • Connect the RED lead on the feeder to terminal A on the LWCO 3) Using McDonnell & Miller WF2-U-24 feeder - Do not alter factory boiler wiring. Connect WF2-U-24 to CG400A as fol- lows: • Connect terminal W on the feeder to terminal A on the LWCO • Connect terminal N on the feeder to terminal 2 on the LWCO • Connect terminal H on the feeder to terminal 1 on the LWCO Feeder Wiring for Boilers Equipped with McDonnell & Miller #67 Low Water Cut-offs Figures 14a and 14b show feeder wiring for McDonnell & Miller #101A, McDonnell & Miller WF2-U-24 and Hydrolevel VXT-24 feeders on boilers equipped with #67 low water cutoffs. The following points apply to all feeder wiring to #67 low water cut-offs: • Use a separate transformer to power the feeder. Do not use the transformer on the boiler.
Page 21
CAUTION DO NOT INSTALL JUMPER BETWEEN 2 & 3 ON #67 L.W.C.O. FIGURE 14b: WIRING MCDONNELL & MILLER WF2-U-24 FEEDER OR THREE-WIRE HYDROLEVEL VXT-24 FEEDER TO BOILER EQUIPPED WITH #67 L.W.C.O. FIGURE 15: WIRING INDIRECT WATER HEATER TO BOILER 19 19...
Page 22
Indirect Water Heater Wiring Figure 15 shows field wiring for an indirect water heater. A Honeywell R845A or equivalent DPST relay and transformer is required. The high limit described in Part IX must also be supplied by the installer. A call for heat from the indirect water heater thermostat will energize the relay making both sets of contacts. One set of these contacts then energizes the circulator. The other set of contacts will make the “T” and “T” contacts on the burner primary control, firing the burner. If the boiler water temperature exceeds the high limit setting of 180F, the high limit will open the “T” - “T” circuit and the burner will shut down. If there is a call for space heat, the heating thermostat will make the “T”-”T” circuit and the boiler will fire without regard to the status of the indirect water heater. The low water cut-off and pressure limit control will interrupt 120 volt power to the burner in the event of a low water or excessive pressure condition. BSI Control System – Sequence of Operation (Refer to Figures 16 & 17 for ladder and connection diagrams) Sequence of Operation, Intermittent Ignition 1) When the boiler is energized, 24 volts is immediately applied to terminals “1” (blue) and “4” (yellow) on the vent damp- er. Assuming that there is no call for heat, and that the damper switch is in the “automatic” position, the damper will close. On boilers equipped with Hydrolevel CG400A probe type low water cut-offs, voltage is also always applied to terminals “1” (blue) and “2” (yellow) on the low water cut-off to power the water level sensing circuit. On boilers equipped with #67 float type low water cut-offs, power is always applied to terminal “2” on the #67 LWCO. 2) Assuming that water is above the cut-off level, power will appear at terminal “3” on the CG400 LWCO or terminal “1” on the #67 LWCO. 3) Assuming that steam pressure is below the pressure limit setting, power will appear on one side of relay contact 1R1 (Gray lead). Relay 1R is the R8225 mounted under the junction box. 4) A call for heat from the thermostat energizes relay coil 1R causing contacts 1R1 to make. Current then flows through contacts 1R1 to pin terminal “2” (orange) at the vent damper and the damper opens. 5) Once the vent damper is fully open, an end switch inside the damper will make, energizing pin “3” (red) at the damper. 6) Current passes from terminal “3” on the vent damper though the flame rollout and blocked vent (“spill”) switches. Under normal conditions, both of these switches are made and voltage will therefore immediately appear across terminals “24V”...
Page 23
McDonnell & Miller #67 Low Water Cut-off - Interrupts burner operation if the water in the boiler drops below a safe level. Burner operation is restored when the water level in the boiler is raised above the cut-off point. The vent damper will close when the low water cut-off interrupts burner operation. Pressure Limit Control - Interrupts burner operation when the pressure in the boiler exceeds the “Cut-in” setting plus the differ- ential setting. The “Cut-in” setting is shown on the outside of the control and is adjusted using the screw on the top of the control. The differential is adjusted using the white thumb wheel on the inside of the control. Burner operation is restored when the pres- sure in the boiler drops to the “Cut-in” pressure. The vent damper will close when the pressure limit control interrupts burner operation. Blocked Vent (“Spill”) Switch - Automatically interrupts burner operation in the event that flue gas spills from the draft diverter opening. This switch is equipped with a reset button which must be pressed to restore normal burner operation. An open blocked vent switch is indicative of a problem with the vent system. If the blocked vent switch opens, the cause of the venting problem must be found and corrected by a qualified gas service technician before the blocked vent switch is reset. Flame Roll-out Switch - Automatically interrupts burner operation when flames or excessive heat are present in vestibule. The flame roll-out switch is a single use device which must be replaced by an identical switch in order to restore normal operation. An open flame roll-out switch is usually indicative of a plugged heat exchanger. The cause of the flame roll-out must be found and corrected by a qualified gas service technician, and the switch replaced with an identical one, before the boiler is returned to operation. VENT DAMPER (NOTE 2) NOTE 3 “BURNER” “BURNER” LESS VENT DAMPER HONEYWELL VR8204/VR8304 SERIES GAS VALVES (BSI069 - 346) ROBERTSHAW 7000DERHC GAS VALVE (BSI380) 2.
Page 24
FIGURE 17: WIRING DIAGRAM, INTERMITTENT IGNITION AND McDONNELL & MILLER MODEL #67 LOW WATER CUTOFF 22 22...
XI Start-up and Checkout WARNING DO NOT LEAVE THE BOILER IN SERVICE IF IT FAILS ANY OF THE FOLLOWING START-UP CHECKS. DOING SO MAY RESULT IN FIRE, EXPLOSION, OR CARBON MONOXOIDE (CO) POISONING. WARNING • GAS LEAKS MAY RESULT IN FIRE OR EXPLOSION. •...
Page 26
15) Run gas valve safety shutdown test. With main burners firing, disconnect ignition cable from ignition module. Both pilot burner and main burners should stop firing. 16) Check the manifold pressure and adjust if necessary. To do this, use the following procedure: a) Connect a manometer to the inlet pressure tap on the gas valve (see Figure 20). b) Check the inlet pressure with all gas appliances on and off. The inlet pressure at the boiler must be within the following limits regardless of what combination of appliances is firing: Inlet Press (inches w.c.) Natural Gas LP Gas Min. 11.0 Max. 14.0 13.0 If the inlet pressure falls outside of these limits, find and correct the cause of the problem before proceeding further. c) Connect a manometer to the manifold (outlet) pressure tap on the gas valve (see Figures 23 and 24). d) Read the manifold pressure. It should be set at: Natural Gas LP Gas Manifold Press. (inches w.c.) 3.5 10.0 e) If a manifold pressure adjustment is needed, make the adjustment by turning the pressure regulator (see Figures 23 and 24) screw clockwise to raise the pressure and counter clockwise to reduce the pressure. If a manifold pressure adjustment is made, recheck the line pressure to be certain that it is still within acceptable limits. Replace the cover screw on the regulator. FIGURE 18: INTERMITTENT IGNITION PILOT BURNER FLAME 24 24...
Page 27
LIGHTING INSTRUCTIONS FOR BOILERS EQUIPPED WITH HONEYWELL VR8204 AND VR8304 SERIES GAS VALVES FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A.
Page 28
LIGHTING INSTRUCTIONS FOR BOILERS EQUIPPED WITH ROBERTSHAW 7000DERHC SERIES GAS VALVES FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A.
Page 29
FIGURE 19b: MAIN BURNER FLAME - 40mm FIGURE 19a: MAIN BURNER FLAME - 1” BURNERS (“HIGH ALTITUDE”) BURNERS 17) Test thermostat operation while the boiler is running. Turn the thermostat to the lowest setting. Both pilot burner and main burners should stop firing. Raise the thermostat back to the highest setting. The pilot burner and main burners should relight. 18) Verify low water cutoff operation while the boiler is running. Slowly open drain valve and drain boiler until the water level drops below low water cutoff line. Water still should be visible in the gauge glass when the low water cutoff shuts down the main burners. Both pilot burner and main burners should stop firing. Make sure pressure limit, thermostat or other controls have not shut off the boiler. Upon test completion refill the boiler to the normal water level. 19) Check pressure limit control operation. When steam pressure is registered on pressure gauge, lower pressure limit setting below gauge reading. Both pilot burner and main burners should stop firing. Raise pressure limit setting above gauge reading. The pilot burner and main burners should relight. 20) After the boiler has operated for approximately 30 minutes, check the boiler and heating system piping for leaks. Repair any leaks found at once. 21) Inspect the vent system for flue gas leaks. Repair any leaks found before leaving the boiler in operation. 22) Replacement of a steam boiler tends to break loose accumulated scale from the system. During the first week of operation, blow down the #67 low water cut-off at least three times following the blow down instructions on the yellow sticker adjacent to the low water cut-off. 23) After new boiler has been installed and put into continuous operation for several days, clean the boiler of oil, grease, sludge, and other contaminants that may have been present in existing piping. This will prevent unsteady water line and water carry over into supply main. The boiler boil-out should be done as follows: a) Turn off gas supply to boiler per the appropriate Lighting and Operating instructions on page 25 - 26. b) Drain water from boiler until about one inch of water is visible in gauge glass. c) Run a hose or temporary piping from the boiler drain valve to a location where hot water can be safely discharged. Drain approximately five gallons of water from the boiler and mix-in an appropriate amount of an approved boil- out compound. Remove safety valve and refill the boiler with prepared solution through funnel inserted into elbow under the safety valve. Run a hose or temporary piping from safety valve tapping to a location where hot water can be safely discharged. DO NOT INSTALL ANY VALVES IN THIS LINE. d) Light off the boiler per the appropriate instructions on page 25 - 26. Run boiler for several hours, boiling the water, without generating steam pressure. Open the water feed valve sufficiently to allow a slight overflow of water through the safety valve tapping drain line. Continue boiling until water coming out is clear.
Page 30
f) Reinstall safety valve and related piping. g) Conduct pH and Alkalinity test of water in the system. The pH reading should be in 7 to 11 range. NOTE When substantial amount of make-up water is used due to lost condensate, or when make-up water is hard or corrosive, water treatment is required. Contact qualified water treatment company for recommended water treatment compounds and procedures. FIGURE 20a: GAS VALVE DETAIL - HONEYWELL VR8204 AND VR8304 FIGURE 20b: GAS VALVE DETAIL - ROBERTSHAW 7000DERHC 28 28...
XII Service and Maintenance WARNING • THE BOILER CONTAINS REFRACTORY CERAMIC FIBER, A POSSIBLE HUMAN CARCINOGEN. USE A NIOSH APPROVED RESPIRATOR WHEN SERVICING HIGH-TEMPERATURE INSULATION AND GASKET MATERIALS. WASH EXPOSED SKIN GENTLY WITH SOAP AND WATER AFTER CONTACT. WASH EXPOSED CLOTHING SEPERATE FROM NORMAL LAUNDRY.
Page 32
bristle brush and then vacuuming out any debris through the venturi opening. 5) Inspect the pilot assembly. Clean any deposits found on the electrode and grounding strap. The ideal gap between the electrode and the ground strap is 1/8”. Inspect the porcelain for cracks or other deterioration. Replace pilot assembly if dete- rioration is found. 6) Inspect the combustion chamber insulation for deterioration. 7) Inspect the ignition cable insulation for cracks or other deterioration. If deterioration is found, replace cable. 8) Reinstall burners, being careful to put the pilot burner back in its original location. 9) Inspect all boiler wiring for loose connections or deterioration. 10) Inspect the vent system: • Make sure that the vent system is free of obstructions. • Make sure that all vent system supports are intact. • Inspect joints for signs of condensate or flue gas leakage. • Inspect venting components for corrosion or other deterioration. Replace any defective vent components. 11) Inspect the boiler and system for leaks. 12) Inspect the low water cut-off: • For Hydrolevel CG400A low water cut-offs - Remove and inspect the probe for scale and sediment buildup. Clean any sediment or scale from the probe with a scouring pad or steel wool. Consult the Hydrolevel CG400 manual for any additional maintenance information. Test the low water cut-off before placing the boiler back into service. • For McDonnell & Miller #67 low water cut-offs - Remove and inspect switch and float mechanism. Inspect float bowl for mud accumulation. Clean as required. Replace the switch and float mechanism every five years or 100,000 cycles. Consult the McDonnell and Miller #67 manual for any additional maintenance information. Test the low water cut-off before placing the boiler back into service. 13) Allow the boiler to cool to room temperature. Remove the drain valve and 2 x 3/4 bushing on the left side of the boiler. Use a flashlight to inspect the bottom row of pushnipples for accumulated scale or mud. If a significant amount is present, use the following procedure to clean the inside of the heat exchanger: a) Temporarily install a 1 1/4 inch or larger full port ball valve in place of the boiler drain. Temporarily pipe the outlet of this valve to a location where hot water and steam can be safely discharged.
Page 33
14) Place the boiler back in operation using the procedure outlined in “Start-up”. Check the pilot line and any other gas pip- ing disturbed during the inspection process for leaks. Heat Exchanger Cleaning Procedure WARNING SOOT DEPOSITS IN THE FLUE PASSAGES ARE A SIGN THAT THE BOILER MAY BE OPERATING AT HIGH CARBON MONOXIDE (CO) LEVELS. AFTER CLEANING THE BOILER OF SOOT DEPOSITS, CHECK THE CO LEVEL IN THE FLUE GAS TO INSURE THAT THE BOILER IS OPERATING PROPERLY.
XIII Troubleshooting The following pages contain troubleshooting charts for use in diagnosing control problems. To use these charts, go to the box marked “Start” at the top of the chart on page 34 or 36 and follow the appropriate path though the chart until a box with a list of possible causes is reached. If the problem is known to be within the ignition system, go directly to the ignition system troubleshooting guide for the boiler on page 38. In using these charts, the following should be kept in mind: 1) These charts are only meant to be used by a professional heating technician as an aid in diagnosing control problems. 2) Where applicable, follow all precautions outlined in the appropriate lighting instructions on pages 25 - 26. 3) In general, these charts assume that there are no loose or miswired electrical connections. Before using these charts, in- spect all electrical connections on the boiler to make sure that they are tight. Also, check the wiring on the boiler against the appropriate wiring diagram in Figures 16 - 17. 4) The possible causes at the end of each branch in these charts are not listed in order of likelihood. All controls on the BSI are tested at least once in the manufacturing process and a defective control or component is generally the least likely cause. Before replacing a component, try to rule out all other possible causes. 5) These troubleshooting charts assume that the vent damper is closed at the beginning of the troubleshooting process. With the 120 volts applied to the boiler and no call for heat, the damper should go to the closed position. If it does not, do the following: • Confirm that 120 volts is applied to the boiler and that there is no call for heat. • Make sure that the switch on the damper is in the “automatic” position. • Unplug the harness from the damper and check for 24 volts across pin #1 (blue) and pin #4 (yellow). • If voltage is present, the damper is defective or there is an obstruction in the path of the damper blade. • If no voltage is present, there is either a loose connection in the damper harness or the transformer is defective. 6) If the charts indicate that the transformer is defective, it is possible that this transformer has been destroyed by a short circuit in the boiler wiring. Before replacing the transformer, carefully inspect all low voltage wiring on the boiler for places where it is touching the frame of the boiler or wiring on the other side of the transformer. 7) If the charts indicate that the R8225 relay is defective, there is a good chance that a second transformer is present in the thermostat circuit, resulting in the application of 48 volts across the relay coil. In older buildings, this transformer may be hidden in a location far from the boiler. If this second transformer exists, it must be found and removed before the R8225 is replaced.
Page 36
Troubleshooting Chart for BSI Boilers Equipped with Hydrolev- el CG400A Low Water Cut-offs and Vent Dampers Caution: Read page 33 before attempting to use this chart START Vent damper open? Is there an audible Thermostat click as R8225 relay calls for heat pulls in when the thermostat calls for heat?
Page 37
Do burners Do burners shut Main shut down when down when water burners pressure level drops below light? exceeds limit cut-off point? setting? 24 volts across red damper lead * Defective damper * Defective and yellow * Defective or loose pressure limit transformer lead? damper harness...
Page 38
Troubleshooting Chart for BSI Boilers Equipped with McDon- nell & Miller #67 Low Water Cut-offs and Vent Dampers Caution: Read page 33 before attempting to use this chart START Vent damper open? Is there an audible Thermostat click as R8225 relay calls for heat pulls in when the thermostat calls for...
Page 39
Do burners Do burners shut Main shut down when down when water burners pressure level drops below light? exceeds limit cut-off point? setting? 24 volts across red damper lead * Defective damper * Defective and yellow * Defective or loose pressure limit transformer lead? damper harness...
Page 40
Ignition System Troubleshooting Chart Caution: Read page 33 before attempting to use this chart START (24 volts is present across 24V and 24V (GND) on ignition module but main burners do not light) Spark Does Main spark stop across Pilot burner ignitor/sensor lights?
XIV PARTS The following parts may be obtained from any Crown distributor. To find the closest Crown distributor, consult the area Crown representative or the factory at: Crown Boiler Co. Customer Service P.O. Box 14818 Philadelphia PA. 19134 www.crownboiler.com For boilers installed at elevations above 2000 ft, consult the local Crown representative or the factory for the correct main burner orifice. QUANTITY PER BOILER OR CROWN P.N. QTY. OR KEY # DESCRIPTION CROWN P.N. BSI HEAT EXCHANGER ASSY. 1 ea. 850013 850014 850015 850016 850017 850018 850019 850020 850021 850022 BSI/CWI LEFT END SECTION 750001...
Appendix A: Knockdown Boiler Assembly Instructions A. Before Installing 1) Thoroughly inspect the cast iron heat exchanger for any shipping damage, i.e. cracks in the castings, broken lugs or punctures due to mishandling. 2) Do not use the heat exchanger if there is any damage to it. 3) Inspect the joints between the sections for openings. Reseal any openings with high temperature silicone sealant.. 4) Keep the base in the shipping carton until it is time to perform the assembly. This keeps foreign material from contaminating the burners or creating other hazards. Do not use the base assembly if there are any signs of visible damage. 5) Review all of the installation requirements in this installation manual. B. Base Assembly Preparation 1) The combination base-burner-manifold is shipped assembled from the factory. (The combination gas valve is shipped assembled and can be found in the “Base Box”.) 2) Smear a thin layer of silicone in several places across the top of the base to adhere the fiber gasket strip. 3) Install the fiber gasket strip, which was shipped in the “Base Box” (Figure A1). 4) Place the base assembly in the location where the boiler is to be installed. Refer to Section III and IV in the instal- lation manual for additional information on placement. C. Heat Exchanger and Flue Collector Installation 1) Position the heat exchanger above the base with the return connection located toward the front of the boiler and the lugs, located on each end of the boiler, centered over the studs, which are on each end of the base (Figure A1). Lower the heat exchanger over the studs, taking care not to disturb the studs which may push out if the heat exchanger comes in contact with them. Also, take care not to disturb the ceramic fiber gasket. 2) Once the heat exchanger has been placed on the base, inspect the gasket for proper seal. Repair or replace gasket if necessary. 3) Secure the heat exchanger with 5/16” lock nuts with nylon inserts and washers from the hardware bag.
Page 50
5) Install the left side panel in the same manner as the right side. 6) Attach the front corners of the diverter panel to the side jacket panels using #10 sheet metal screws. 7) Install the horizontal (angle) jacket clips in the front edge of the side jacket panels. Slide this clip through the rect- angular slot that is about halfway up the front edge of the side jacket panels and secure with the 8-32 self tapping screws provided. 8) Slip the Vertical Jacket Clip through the rectangular slot that is near the bottom of the front edge of the side jacket panels. Secure with the 8-32 sheet metal screws provided. 9) Install the top jacket panel. Use #10 sheet metal screws to attach it to the rear jacket panel and the top-front corners of the side panels. 10) Install the upper-front jacket panel. Insert the flange on the top of this panel under the top panel. Run two #10 sheet metal screws into the horizontal jacket clips through the holes in the bottom of this panel. 11) Attach the door knobs to the Lower-Front Panel using 8-32 x 1/2 machine screws. 12) The labels have been applied at the factory. Verify the location of the labels according to the list below: a) Clearance Label - Located on the top jacket panel. b) Lighting Instructions - Located on the lower left corner of the right side panel next to the gas manifold c) Lowest Permissible Water Level Plate - Located next to the bottom water gauge tapping. d) Blow Down Card - Located just above the “Lowest Permissible” Water Level Plate e) Wiring Diagram - Located on the inside of the removable door f) “CROWN” Nameplate - Located on the top center of the outside of the removable door g) Rating Plate - Located on the upper left of the right side panel D. Gas Valve Installation 1) The gas valve assembly has been pre-piped with one half of a piping union and is to be connected to the other half of the union located on the gas manifold.
Page 52
F. Electrical Wiring Connections (Also refer to wiring diagrams in Part X of the installation manual) 1) A pre-wired junction box assembly specific to the control package ordered with the boiler has been provided by the fac- tory. 2) Orient the junction box so the black relay, which is mounted to the outside of the junction box, is facing down. 3) Mount the junction box assembly to the right side jacket using the holes provided (See Figure 1 in the installation manual).
Page 53
FIGURE A3: TAPPING LOCATIONS (SEE TEXT FOR TAPPING USES) 51 51...
Need help?
Do you have a question about the BSI103 and is the answer not in the manual?
Questions and answers