Failure to regularly blow down the float type low water cut-off can result in severe damage to boiler.
If it is necessary to either manually or automatically add water to the boiler more than once a month, a qualified
gas service technician should inspect the system for leaks or defective vents. Frequent additions of fresh water
could result in severe damage to boiler.
Figure 3: Float Type Low Water Cut-off
7) Auxilary Controls – Many boilers are installed with equipment not supplied with the boiler, but which is criti-
cal for safe, reliable operation of the boiler. Some examples of this type of equipment include:
Zone Controls
Boiler Feed Pumps
Draft Inducers and Power Venters
Motorized Combustion Air Louvers
Make sure that this equipment is maintained in accordance with its manufacturer's instructions.
Lighting instructions for all boilers appear on the following pages. These instructions are listed by the model of the
gas valve used. The table below references the boiler model to the gas valve used and the page on which the appropri-
ate lighting instructions may be found.
Boiler Model
AWR038E - AWR280E
CWI103E - CWI346E
BSI069E - BSI346E
BWF069E - BWF229E
CWD060 - CWD245
CWI-380E
BSI-380E
BWC070-BWC425
* Gas valve numbers are to reference lighting instructions only. Do not use this chart as a
replacement parts list.
CAUTION

Lighting Instructions

Ignition System
Gas Valve *
Honeywell VR8204 or
VR8304
Intermittent Pilot
Robertshaw
7000DERHC
Honeywell VK8115 or
Direct Spark
Dungs GB-WND
4
Lighting
Instructions on
Page:
5
6
7