Crown Boiler AWR Series Installation Instructions Manual page 44

Gas-fired natural draft hot water boilers
Table of Contents

Advertisement

Error
Code Meaning
Low Flame Signal
4
Pilot Flame detected when no
6
flame should be present
Internal electronics failure
18
Flame sensed during 1.7s pre-
23
purge (before pilot valve opened)
Boiler water temperature sensor
32
failure
35
Duplicate Zone
Damper failed to open after 60s
55
Power at end of limit string when
56
it shouldn't be.
Grounded pilot electrode
57
58
AC Power Frequency Error
Line voltage error
59
(Supply voltage too high or low)
Thermostat input higher than
60
threshold
Line Voltage Unstable
61
63
Maximum recycles exceeded
64
Internal failure
EnviraCom communication lost
89
TABLE 13.0 - ERROR CODES
Possible Cause
Low gas pressure at gas valve inlet
Partially plugged pilot tubing or pilot orifice
Loose connection in ignition cable or ground wiring
Dirty pilot electrode/ground strap
Pilot electrode porcelain cracked
Damaged pilot hood/ assembly
Defective control
Defective gas valve
High gas pressure
Defective control
Possible internal problem with boiler control. Cycle power to the boiler and replace
control if problem persists.
Defective gas valve
High gas pressure
Defective control
Loose sensor connection at control
Defective Sensor
Defective control
Error code reserved for future use
Loose or defective damper harness
Obstruction in path of damper blade
Defective damper
Defective control
Control, vent damper, or damper harness is defective. With Error 56 present, and no
call for heat, unplug damper harness from control and check for 24VAC between ter-
minal P6-5 on control (see Figure 9.2 for location) and ground. If voltage is present,
replace control. If not, inspect the damper harness for shorts or miswired connections.
If no harness defect is found, replace vent damper.
Condensate or foreign material is shorting pilot electrode to ground.
Ignition cable insulation is damaged and touching ground.
Pilot is damaged
120VAC power supply frequency is incorrect (Should be 60Hz)
120VAC power supply is dirty (consult electrician and/or Utility)
Boiler water temperature sensor common (center wire) is damaged and shorted to
ground
Power supply voltage is incorrect (should be 120VAC nominal)
Defective or incorrect 24VAC transformer
Loose 120VAC connection or 24VAC connection between transformer and control
External voltage is applied to thermostat connections (most common cause is external
transformer in old thermostat wiring.
120VAC power supply is dirty (consult electrician and/or Utility)
Loose 120VAC connection or 24VAC connection between transformer and control
Large electrical loads elsewhere on the installation are switching on and off, causing
incoming voltage to swing excessively at boiler.
See Error Code 4 above (boiler lost proof of pilot 6 times in a row)
Loose or defective damper harness
Obstruction in path of damper blade
Defective damper
Improper pilot operation
If problem persists, replace control
Communication lost between boiler control and EnviraCom thermostat
44

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents