Product Description; Specifications - Crown Boiler AWR Series Installation Instructions Manual

Gas-fired natural draft hot water boilers
Table of Contents

Advertisement

The AWR series boiler is a cast iron gas fired water boiler designed for use in closed forced circulation heating systems.
This boiler is a Category I drafthood equipped appliance, which must be vented by natural draft using a lined masonry
or listed metal chimney system. An adequate supply of air for combustion, ventilation and dilution of flue gases must be
available in the boiler room.
FIGURE 2.1: GENERAL CONFIGURATION
BWF Space Heating Ratings
Basic
Input
Boiler
(3)
Model
MBH
AWR038B
38
AWR070B
70
AWR105B
105
AWR140B
140
AWR175B
175
AWR210B
210
AWR245B
245
AWR280B
280
(1)
Input ratings can be used for elevations up to 2000 ft above sea level. Refer to Appendix A for elevations 2000 ft or higher.
(2)
Net AHRI Water Ratings shown are based on a piping and pickup allowance of 1.15. Consult manufacturer before selecting boiler for
installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
(3)
Add Suffix N for Natural Gas or Suffix L for Propane Gas to basic Boiler Model shown (Example: AWR210BN, AWR210BL)
I Product Description
II Specifications
TABLE 2.2 SPECIFICATIONS
Net AHRI
Heating
Rating,
(1)
Capacity
Water
(2)
MBH
MBH
32
28
59
51
88
77
117
102
146
127
176
153
205
178
234
203
'A'
'B'
Width
Width
AFUE
%
(inch)
(inch)
84.0
2
9-3/4
31-1/2
84.0
3
12-7/8
31-1/2
84.0
4
15-3/8
31-1/2
84.0
5
18-1/2
31-1/2
84.0
6
21-1/2
31-3/4
84.0
7
24-5/8
33-1/2
84.0
8
27-5/8
33-1/2
84.0
9
30-3/4
33-1/2
5
Connection
Size
Water
Content
'C'
Gas
Vent
(inch)
(NPT)
(gal)
4
1/2
1
4
1/2
2
5
1/2
3
6
1/2
4
7
1/2
5
7
3/4
6
8
3/4
7
8
3/4
8
Approx.
Shipping
Weight
(lbs)
234
284
334
384
434
484
533
583

Hide quick links:

Advertisement

Table of Contents
loading