Additional encoder actual value Gx_XIST2
Error codes in Gx_XIST2 where G1_ZSW, Bit 15 = 1
Table 4-3
G1_XI
ST2
1
Hex
2
Hex
4.4.4

I/O addresses

Precondition
For communication between the controller and the individual axes of an ADI4 DP slave, it is
necessary that the setpoint and the actual value of an axis have the same I/O addresses.
HW Config takes this requirement into account automatically when an ADI4 DP slave is inserted
in the configuration.
Inserting I/O addresses
1. In the "DP Slave Properties" dialog box, select the "Configuration" tab.
2. Under PROFIBUS partner, I/O addr. enter: <I/O address>.
3. Click on "OK".
Note
• The setpoint and actual value of an axis must have the same I/O address.
• If an ADI4 DP slave is inserted into an S7 project using a copy operation, e.g. from another
• To avoid access conflicts between PROFIBUS DP drives and I/O modules, the following
SIMOTION ADI4 - Analog Drive Interface for 4 Axes
Equipment Manual, 07/2017, A5E33446849B
Error codes in Gx_XIST2
Meaning
Possible causes/description
Encoder sum
The encoder signal levels are too low, faulty (inadequate shielding) or cable
error
breakage monitoring has been tripped.
Zero mark
A fluctuation in the measured rotor position has arisen between two encoder
monitoring
zero marks (encoder pulses may be lost).
I address (actual value) = O address (setpoint)
S7 project, then HW config directly assigns the I/O addresses. This may have the
consequence that an axis is assigned different I/O addresses for setpoint and actual
values. In this case, the I/O addresses must be corrected manually.
values must be used for I/O addresses for the ADI4 DP slave:
– NCU 7x0.2 DP: ≥ 272
– NCU 7x0.3 DP: ≥ 1024
Parameter assignment
4.4 PROFIBUS parameters