Homing Using Encoder Zero Mark And Homing Output Cam - Siemens SIMOTION ADI4 Equipment Manual

Analog drive interface for 4 axes
Hide thumbs Also See for SIMOTION ADI4:
Table of Contents

Advertisement

4.5.10

Homing using encoder zero mark and homing output cam

System structure
Figure 4-7
Function
The homing output cam signal must be connected to a digital input on the ADI4 (X6-2, Pins 2 to
5). The homing output cam signal is processed in the controller as part of the homing operation.
Once the homing output cam signal is detected, the controller reduces the axis velocity to the
homing approach velocity and requests the ADI4 to home to the next encoder zero mark. Once
the request is detected, the ADI4 transmits the actual encoder value to the controller as the
home position the next time it detects an encoder zero mark.
Without 611U conformant mode
No further measures are required.
With 611U conformant mode
The relevant signal for the axis to be homed (e.g. Axis 1) must be set in the digital output word:
• Digital output word:
Bit 0: = 0 ⇒ "Axis 1: Zero mark of Encoder 1 (X4-1)"
SIMOTION ADI4 - Analog Drive Interface for 4 Axes
Equipment Manual, 07/2017, A5E33446849B
Basic system structure: Homing using encoder zero mark and external zero mark
Parameter assignment
4.5 Function parameters
59

Advertisement

Table of Contents
loading

Table of Contents