BeaconMedaes 4107 9006 25 Installation, Operation And Maintenance Instructions page 74

Scroll laboratory air compressor system
Table of Contents

Advertisement

"Oil-Less" Scroll Laboratory Air
Appendix C: TotalAlert Embedded Control System
Figure C.34 Website Setup
1. Click Website Setup to access the Website
Setup page.
2. Select a time interval from the pull-down list
of options.
3. Click the Submit button.
C.7.9 System Trend Setup
Figure C.35 System Trend Setup
This System Trend Setup page (Figure C.35) is
used to confi gure the trend log for the website and
to allow the data to be cleared. The System Trend
screen contains a maximum of 720 events for each
of the items recorded, so the actual duration of the
trend log changes with the time interval selected.
The durations available to select are 6 hours, 24
hours, 2.5 days, and 10 days.
4107 9006 25.11
1. Click System Trend Setup to access the System
Trend Setup page.
2. Select a time interval from the pull-down list
of options.
3. Click the Submit button.
C.7.10 Electronic Notifi cation Setup
This Electronic Notifi cation Setup page (Figure
C.36) is used to confi gure the Electronic Notifi cation
feature of the TotalAlert Embedded control
system. By setting up the Electronic Notifi cation,
key personnel can receive notifi cations of all alarm/
shutdown alerts and/or all maintenance alerts
(e-mail, pager, phone text message). The device
acts as an SMTP client. An SMTP server is required
for electronic notifi cation to function.
Figure C.36 Electronic Notifi cation Setup
1. Click Electronic Notifi cation Setup to access
the Electronic Notifi cation Setup page.
2. Select Enable to enable the e-mail notifi cation
tool.
3. Enter up to fi ve email addresses.
C-18

Advertisement

Table of Contents
loading

Table of Contents