Table 5.
Calculating actual VA requirements (continued)
Item
Below is an example VA draw calculation for a BACnet MS/TP controller on a cooling-only VAV box:
Description
• Symbio no I/O
• Setpoint and Zone Temperature Sensor Input
• Air Flow Sensor Input
• Occupancy Input
• Binary Out for Air Damper (only one energized at a time, not
including actuator draw)
• Trane F Series Air Damper Actuator (Taken from
Total
Below is an example VA draw calculation for a BACnet IP controller on a hot water reheat VAV box:
Description
• Symbio 210e
• Setpoint and Zone Temperature Sensor Input
• Air Flow Sensor Input
• Binary Out for Water Valve (only one energized at a time, not
including actuator draw)
• Belimo Hot Water Actuator (TR24-3)
• Binary Out for Air Damper (only one energized at a time, not
including actuator draw)
• Trane F Series Air Damper Actuator (Taken from
Total
Below is an example VA draw calculation for a BACnet Zigbee controller with XM on a hot water reheat VAV box:
Description
• Symbio 210
(c)
• Air-Fi WCI (X13790901030)
• Air Flow Sensor Input
• XM32
• Binary Out for Water Valve (only one energized at a time, not
including actuator draw)
• Belimo Hot Water Actuator (TR24-3)
• Binary Out for Air Damper (only one energized at a time, not
including actuator draw)
• Trane F Series Air Damper Actuator (Taken from
Total
(a) Insignificant load.
(b) See device connected to DC supply for current draw.
(c) Older WCI version draw more current than current design.
Table 6.
Style
F - Style Actuator
Air Valve Actuator C through E Style
Fan Power Fan Output
Hot Water Proportional
Hot Water 2 Position
Electric Heater Magnetic Contactor
Electric Heater Mercury Contactor
BAS-SVX084A-EN
Sub
Table 7, p.
16)
Table 7, p.
16)
Table 7, p.
16)
Replace the control box cover after field wiring to prevent any electromagnetic interference.
Review
Table 7
for factory-installed components and voltage amperage.
Binary load values
VA Draw Per I/O (24 Vac)
Draw
• 8.0 VA
• 0 VA
• 0.3 VA
• 0.1 VA
• 0.1 VA
• 4.0 VA
12.5 VA
Draw
• 9.5 VA
• 0 VA
• 0.3 VA
• 0.1 VA
• 1.0 VA
• 0.1 VA
• 4.0 VA
15 VA
Draw
• 8.0 VA
• 0.5 VA (10 mA WCI power draw)
• 0.3 VA
• 5.0 VA (100 mA XM32 power draw)
• 0.1 VA
• 1.0 VA
• 0.1 VA
• 4.0 VA
19 VA
Volt Amps
4 VA
12 VA
6 VA
4 VA
6.5 VA
10 VA
12 VA
Wiring Installation
Maximum Total VA Draw (24
Vac)
15