Table 10. Marquee LED status and error codes
LED Blink Pattern
12
15
18
19
21
22
24
25
26
27
31
32
Red LED Blink
Pattern
34
39
42
44
48
49
54
57
59
62
64
Note: *Patch firmware updates will cause the same error codes.
BAS-SVX084A-EN
Message
Attempted load of the field kernel or device
Load Field Fail
tree failed.
Load Recovery Fail
Attempted load of the recovery image failed. Replace controller
Failed to mount the field partition during a
Field Mount Fail
firmware update attempt.
Rotary switches are set to a bad/unknown
Bad Switch Setting
value.
Bad Firmware File
Unable to mount the firmware update file.
Firmware file downloaded is not compatible
Firmware Not Compatible
with this hardware.
Field Format Fail
Failed to reformat the field file system.
Field Attach UBI Fail
Failed to attach (UBI) to the field file system. Replace controller.
Field Mount Fail
Failed to mount the field file system.
Bad Update Method
Don't know what our update method is.
No Firmware File Found
Unable to find a firmware update file.
Multiple Firmware Found Multiple firmware update files were found.
Firmware Invalid
Firmware Invalid
Bad Firmware File
Unable to mount the firmware update file.
Restore Failed
Database restore failed for some reason.
Crashed too many times and are now
Hold
"holding."
The embedded application terminated
Abnormal Termination
abnormally.
The firmware file downloaded is not
Firmware Not Compatible
compatible with this hardware.
Kernel Update Failure
Failed to update the kernel.
Device Tree Failure
Failed to update the kernel device tree.
Bootloader Failure
Failed to update the bootloader.
Recovery Failure
Failed to update the recovery file system.
Description
Controller LEDs
Action by User
1.
Thumb drive with .scfx file,
power down, set address
rotaries to 991, and power up.
2.
Replace controller.
1.
Thumb drive with .scfx file,
power down, set address
rotaries to 991, and power up.
2.
Replace controller.
Contact technical support.
Download firmware file again and
retry download.
Download the correct FW file for the
controller.
Replace controller.
Replace controller.
Contact technical support.
Thumb drive has no .scfx file. .scfx
file must be located at the root of
the USB drive.
Too many .scfx files on the thumb
drive. Can only have on .scfx file
and must be located in the root of
the USB drive.
Download the firmware file again
and retry download.
Download the correct FW file again
and retry download.
Download the firmware file again
and retry download.
Try to restore using a different
backup file (Restore file may be
corrupt).
Contact technical support.
Contact technical support.
Download the correct FW file for the
controller.
1.
Try upgrading the controller
firmware again.
2.
Replace controller.
Not applicable for 210, 400, or 600.
1.
Try upgrading the controller
firmware again.
2.
Replace controller.
1.
Try upgrading the controller
firmware again.
2.
Replace controller.
31