Trane Symbio 210 Installation, Operation And Maintenance Manual page 52

Table of Contents

Advertisement

Calibration, Operation Modes, and Control
Table 14. Unoccupied VFC control, freeze protection for hot water reheat
Controller
Air Valve
Operation
Position
Networked and
valid
Closed no
communicated
flow
supply air
temperature
Stand-alone, coil
temperature
Closed no
sensed at
flow
discharge air
(a)
temperature
(a) Place the discharge temperature sensor in close proximity to the hot water coil discharge. The sensor effectively reports coil temperature when there
is no airflow through the coil. Therefore, the coil can be freeze protected by the discharge air temperature sensor.
Stand-alone Controller Freeze Protection
Controllers operating without communications do not have the source temperature available to
them. In these cases, the discharge air temperature sensor is assumed to provide a reasonable
representation of the coil temperature at conditions with no airflow, if the sensor is close to the coil.
If the discharge air temperature (at no airflow) falls below the configured outdoor air low limit, the
hot water valve is fully opened. The hot water valve remains OPEN until the discharge air
temperature is 10°F above the configured outdoor air low limit or occupied operation begins. If the
communicated source temperature is invalid and the local discharge air temperature sensor has
failed, freeze protection is active and the water valve is open.
Unoccupied Ventilation Flow Control
The controller closes the air valve and the local electric heat and hot water heat are disabled. The
hot water valves OPEN, if needed for freeze protection. The operation of freeze protection for local
hot water heat depends on whether the controller is operating as a network controller or a stand-
alone controller.
52
Condition
Communicated supply air temperature greater than configured outdoor air low limit.
Communicated supply air temperature less than or equal to configured outdoor air low limit,
freeze protection active diagnostic (with 10°F hysteresis).
Discharge air temperature greater than configured outdoor air low limit.
Discharge air temperature less than or equal to configured outdoor air low limit, freeze
protection active diagnostic (with 10°F hysteresis).
Hot Water Valve
Position
Closed
Open to 100%
Closed
Open to 100%
BAS-SVX084A-EN

Advertisement

Table of Contents
loading

Table of Contents