Cooling System - H3C SecPath F1000-AI-X0 Installation Manual

Hide thumbs Also See for SecPath F1000-AI-X0:
Table of Contents

Advertisement

Substance
NOTE:
Dust particle diameter ≥ 5 µm
The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion
and premature aging of components, as shown in Table1-3.
Table1-3 Harmful gas limits in an equipment room
Gas
SO
2
H
S
2
NH
3
Cl
2
NO
2

Cooling system

For adequate cooling of the firewall, follow these guidelines:
Install the firewall at the installation site with its airflow direction meeting the ventilation
requirements.
Reserve a minimum clearance of 100 mm (3.94 in) around the inlet and outlet air vents.
Make sure the installation site has a good cooling system.
The F1000-AI-10 firewall provides front side-intake and rear side-exhaust airflow for heat dissipation.
The F1000-AI-20, F1000-AI-30, F1000-AI-50, F1000-AI-60, F1000-AI-70, F1000-AI-80, and
F1000-AI-90 firewalls provide left side-intake and right side-exhaust airflow for heat dissipation.
Figure1-2 Airflow through the F1000-AI-10 firewall chassis
Figure1-3 Airflow through the
F1000-AI-20/F1000-AI-30/F1000-AI-50/F1000-AI-60/F1000-AI-70/F1000-AI-80/F1000-AI-90
firewall chassis
Concentration limit (particles/m
3
Max. (mg/m
)
0.2
0.006
0.05
0.01
0.04
4
3
)