Installation Manual H3C SecPath F1800-A Firewall Table of Contents Table of Contents Chapter 3 Installation ........................3-1 3.1 Installation Flow ......................... 3-1 3.2 Mounting a SecPath to a Specified Place ................. 3-2 3.2.1 Mounting a SecPath into the Rack................3-2 3.2.2 Mounting a SecPath onto the Workbench ..............
Installation Manual H3C SecPath F1800-A Firewall Chapter 3 Installation Chapter 3 Installation 3.1 Installation Flow Start Mount the cabinet (optional) Mount the equipment to the specified location Connect the PGND wire Connect the power cord Connect the equipment to the console terminal...
Installation Manual H3C SecPath F1800-A Firewall Chapter 3 Installation Caution: Before installing a SecPath, make sure that: You have read Chapter 2 carefully. What described in Chapter 2 has been met. 3.2 Mounting a SecPath to a Specified Place 3.2.1 Mounting a SecPath into the Rack Note: The SecPath can be mounted in N68 cabinet provided by Huawei-3Com.
Installation Manual H3C SecPath F1800-A Firewall Chapter 3 Installation Figure 3-2 Installing the brackets Step 3: Mount the equipment to the rack. Lift the SecPath a little higher than the shelf or guides in the rack; Put the SecPath on the shelf or guides;...
Installation Manual H3C SecPath F1800-A Firewall Chapter 3 Installation You should ensure: Keep the workbench stable and the PGND cable is well grounded. Leave the at least 10 cm space around the chassis for heat dissipation. Do not put heavy objects on the chassis.
Installation Manual H3C SecPath F1800-A Firewall Chapter 3 Installation Connect the ground screw to the grounding bar using a PGND cable. It is required that a grounding resistance should be less than 5 ohm. If you install the SecPath in a 19-inch standard rack, you must also ground the rack.
Installation Manual H3C SecPath F1800-A Firewall Chapter 3 Installation supply for the building has been well grounded before connecting the AC power cable. III. Connecting AC Power Cable Step 1: Check that the PGND wire has been properly connected to the ground.
Installation Manual H3C SecPath F1800-A Firewall Chapter 3 Installation Table 3-1 DC power cable pinouts -48 power supply side SecPath side X2 (blue -48V lead) X1.A1 X3 (black BGND lead) X1.A3 Step 1: Check that the PGND wire has been properly connected to the ground.
Page 9
Installation Manual H3C SecPath F1800-A Firewall Chapter 3 Installation Figure 3-8 Console cable For the pinouts of the console cable, refer to “Appendix A.1”. II. Connecting Console Cable Before you configure the SecPath at the console terminal, connect the console cable in the following steps: Step 1: Select a console terminal.
Installation Manual H3C SecPath F1800-A Firewall Chapter 3 Installation 3.6 Connecting the SecPath to a LAN I. Introduction to the Ethernet Interface The SecPath provides the fixed 10/100Base-TX FE interface. For its attributes in detail, refer to the section “1.4.1 RPU".
Installation Manual H3C SecPath F1800-A Firewall Chapter 3 Installation III. Connecting Ethernet Cable Caution: You must connect a cable to the interface with the correct mark. Do not insert it into other interfaces by mistake. When connecting a LAN switch, insert the cable to the 10/100BASE-TX port identified by MDIX.
Page 12
The AUX interface is usually used for remote configuration through dial-up. In this case, you need to connect the local Modem to the remote Modem through PSTN and then to the remote equipment. For the typical networking diagram and configuration procedure, refer to H3C SecPath F1800-A Firewall Operation Manual. 3-11...
Installation Manual H3C SecPath F1800-A Firewall Chapter 3 Installation 3.8 Installation Verification During installing the equipment, you must check the installation each time you power on the SecPath, making sure that: There is enough space around the cabinet for heat dissipation;...