Technical Data - JUMO B 70.1050.0 Operating Instructions Manual

Table of Contents

Advertisement

Available languages

Available languages

6

Technical data

Meas. input
Designation
Resistance
Pt100 EN 60 751
thermometer
Pt1000 EN 60 751
KTY2X-6 (PTC)
Resistance 0 — 3000 Ω
Measuring current with Pt100: 0.2 mA, with Pt1000, KTY2X-6 and resistance: 0.02 mA
Lead compensation is settable via the parameter Lead compensation resistance
Total resistance (sensor+lead) must not exceed 320Ω with Pt100 and 3200Ω with Pt1000, KTY2X-6 and resistance.
Thermo-
Fe-Con J EN 60 584
couples
Fe-Con L DIN 43 710
NiCr-Ni K EN 60 584
-10 to 60 mV
For the voltage input (-10 to 60 mV), the terminal temperature compensation for thermocouples can be used.
Internal terminal temperature compensation can be switched off through the setup program (0°C).
Range
Meas. accuracy
ambient tempera-
ture error
0.1%/ ≤100ppm/°C
-200 to +600°C
0.1%/ ≤100ppm/°C
-200 to +600°C
1%/ ≤100ppm/°C
-50 to +150 °C
3
0.1%/ ≤100ppm/°C
customer table
0.4%/ ≤100ppm/°C
-200 to +999 °C
0.4%/ ≤100ppm/°C
-200 to +900 °C
0.4%/ ≤100ppm/°C
-200 to +999 °C
0.1%/ ≤100ppm/°C
3
customer table
1
/
Recognition of ...
Probe short-
Probe break
circuit
yes
yes
yes
yes
yes
yes
3
= 0Ω
yes
.
2
no
yes
2
no
yes
2
no
yes
3
no
yes
16

Advertisement

Table of Contents
loading

Table of Contents