8 - PARAMETERS
No.
Description
36
Heat recovery unit
Differential pressure sensor on the heat 
37
recovery unit
Heat recovery unit outlet temperature sensor,
38
intake side
90
External generator
92
Coil no.1 pump
93
Coil no.2 pump
99
Configuration locked

8.2 - Setting parameter

No,
Description
100
Language
Date
102
Time
103
104
Air intake ventilation control
105
Air extraction ventilation control
Multiplication factor value of the signal sent
106
by the air extraction fan with pressure control
in the supply air duct
108
Damper opening time delay
110
AHU max flow rate
111
AHU flow rate low limit threshold
112
Air intake fan flow rate setpoint 1
113
Air intake fan flow rate setpoint 2
Air intake fan flow control PID proportional 
114
band (P)
Air intake fan flow rate control PID integral 
115
time (I)
Air intake fan flow rate control PID derivative 
116
time (D)
118
Intake duct pressure setpoint 1
50
Setting
Enumeration
By default
0: Without
1: Plate
as per P1
3: Gradual speed heat
recovery unit
0: Without
1: With
0: Without
1: With
0: None
1: Heater
2: Cooler
0: Without
1: With
0: Without
1: With
0: unlocked
1: locked
Setting
Enumeration
By default
0: French
1: English
2: German
0
3: Spanish
4: Italian
5: Dutch
DD/MM/YYYY
HH/MM
1: Flow rate
1
2: Duct pressure
0: Intake fan control
feedback
1: Intake fan flow rate 
feedback
0
2: Duct pressure
1
180
As per P1
As per P1
As per P1
As per P1
6000
4
0
200
Display conditions
Read-only
P01 = 39HXE or 39HXV
0
or (P01 = 39HXC and P31 Electric 
preheater = without)
0
P28 Coil 1 = Hot water 
or
0
P29 Coil 2 = Hot water
P28 Coil 1 = Cold water 
or
P29 Coil 2 = Cold water
P28 Coil 1 = Cold water or Hot water or 
0
mixed
P29 Coil 2 = Cold water or Hot water or 
0
mixed
0
Unit
Display conditions
P104 Extraction ventilation control
Duct pressure
P104 Exhaust fan ventilation control
= Duct pressure 
and
P37 Differential pressure sensor on 
heat recovery unit = without
P104 Intake ventilation control = 
Duct pressure
and
(P105 Exhaust fan control = Control 
feedback or flow rate feedback)
s
 P26 Isolation damper ≠ Without
m
/h
Visible as read-only
3
m
3
/h
Visible as read-only
P104 Air intake ventilation control = 
m
3
/h
Flow rate
P104 Intake ventilation control = 
Flow rate
and
P160 Setpoint 1/setpoint 2 selection
= time sched/CMS or on/off input or 
m
/h
3
on/off override
and
P161 Application of setpoint 1/
setpoint 2 selection = ventilation or 
temperature + ventilation
P104 Air intake ventilation control = 
m
/h
3
Flow rate
P104 Air intake ventilation control = 
s
Flow rate
P104 Air intake ventilation control = 
s
Flow rate
P104 Air intake ventilation control = 
Pa
Duct pressure
Access
level
3
3
3
3
3
3
3
Access
level
1
1
1
2
= 
2
2
3
3
3
1
1
2
2
2
1