5 - CONNECTION TO A CMS
Next, in the BACnet tab (for BACnet communication), check that this is activated and set the parameters as required.
Once complete, confirm the page, disconnect your PC, restart the PLC and connect it to the network.
For use with Modbus TCP/IP, configure P700 = Modbus TCP. For use with BACnet IP, configure P700 = BACNET IP.
The PLC only manages Bacnet variables in Binary format (address type DXXX) and Analogue format (address type AXXX).
By default the instance number is 77000.

5.3 - LON

Use of LON requires a board (type FTT-10A), supplied pre-loaded by the manufacturer.
The board is factory fitted. If this is not the case, switch off the controller and insert the board in J13 (entitled BMS card or BMS1) on 
the controller.
It may be recharged on-site using the "nxe" file available on request.
1. Connector for the controller
2. Disconnectable terminal for connection of the LonWorks® network (GND, A, B)
3.  Service pin (create a temporary shunt between the 2 terminals to create a service PIN, disconnect this shunt after finishing the 
operation)
4.  Green service LED: state of the node, lit during the pin service, flashing when the board receives a command from the network, if 
permanently lit = board faulty
5.  Red fault LED: signals an installation issue (incorrect connection to the PLC) or communication configuration issue (check parameter 
P700)
Dimensions (mm)
39