8 - PARAMETERS

8.6 - Communication parameters

No.
Description
Selection of the type of communication
700
protocol used on the BMS1 port
Selection of the transmission speed on the
701
BMS1 port
702
Parity on the BMS1 port
703
Number of stop bits on the BMS1 port
Selection of the controller address on the
705
BMS1 bus
706
Control type
Selection of the type of communication
710
protocol used on the BMS2 port
Selection of the transmission speed on the
711
BMS2 port
712
Parity on the BMS2 port
713
Number of stop bits on the BMS2 port
Selection of the controller address on the
715
BMS2 bus
716
Control type
720
pCO address on the pLAN network

8.7 - Calibration

No.
Description
800
Calibration of the air intake fan flow rate sensor
801
Calibration of the air extraction fan flow rate sensor
802
Intake duct pressure sensor calibration
803
Exhaust duct pressure sensor calibration
804
Intake filter differential pressure
805
Exhaust filter differential pressure
808
Supply air duct temperature sensor calibration
809
Internal supply air temperature sensor calibration
810
Calibration of fresh air temperature sensor
811
Return air temperature sensor calibration
813
Calibration of the room air temperature sensor
Calibration of the heat recovery unit outlet
814
temperature sensor, intake side
816
Calibration of CO
Air Quality sensor
2
817
Heat recovery unit DP pressure sensor calibration
Setting
Enumeration
By default
BMS1
0: None
1: MODBUS RTU
2: LON
3: KNX
0
4: MODBUS TCP
5: BACNET IP
6: WEB
0: 1200
1: 2400
3 if P700=1 or 3
2: 4800
2 if P700=2
3: 9600
4 if P700=4, 5 or 6
4: 19200
0: without
1: even
0
2: odd
1
1
0: Local
0
1: Remote
port
1: ModBus RTU
0
0: 1200
1: 2400
2: 4800
3
3: 9600
4: 19200
0: without
1: even
0
2: odd
1
1
0: Local
0
1: Remote
pLAN
1
Setting
Min.
Max.
-5.0
5,0
-5.0
5,0
-5.0
5,0
-5.0
5,0
-3.0
3,0
-3,0
3,0
-200
200
Display conditions
P700 = 1
P700 = 1
P700 = 1
P700 = 1
Unit
Display conditions
P104 Air intake ventilation control = 
Duct pressure
P104 Intake ventilation control = 
Duct pressure
and
P105 Exhaust ventilation control = 
Duct pressure
°C
Sensor present
°C
°C
°C
P149 = with in read-only, modifiable 
°C
from Th-Tune
P38 Temperature sensor upstream of
°C
heat recovery unit = With
ppm
P149 Air quality control = With
P37 Differential pressure sensor on the 
heat recovery unit = With
Access
level
2
2
2
2
2
2
2
2
2
2
2
2
Access
level
3
3
3
3
3
3
3
3
3
3
3
3
3
3
59