Removing An Electronic Module; Changing An Electronic Module During Operation - Pilz PSSu E F 4DI Operating Manual

Hide thumbs Also See for PSSu E F 4DI:
Table of Contents

Advertisement

Installation
5.3.2

Removing an electronic module

Procedure:
}
Press the locking mechanisms [1] together simultaneously.
}
Pull out the electronic module [2].
Schematic representation:
5.3.3

Changing an electronic module during operation

It is possible to change an electronic module during operation. The configuration data is re-
tained when a module is changed.
Effects:
}
System environment A:
}
System environment B:
Operating Manual PSSu E F 4DI(-T)(-R),
21310-EN-08
In the event of a potential FS communication error, the FS section of the PSSu sys-
tem and all relevant I/O-Groups (SafetyBUS p) switch to a STOP condition.
All FS hardware outputs on the PSSu system switch to a safe condition.
The substitute values are used for the modules' FS outputs, with Valid Bits =
FALSE.
CAUTION!
Sparking can cause interference and errors!
Only change the module when the load is switched off!
[1]
[2]
[1]
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pssu e f 4di-tPssu e f 4di-r312200314200315200

Table of Contents