ECL Card settings

(circuit I)
A
Time and date
B
System information
C
Heat curve
Setting ranges
Factory settings
Slope
0.2 ... 3.4
See section 20
Parallel displacement
-9 ... 9 K
See section 20
1
Limit for heating cut-out
10 ... 30 °C
See section 21
2
Flow temperature, min. / max. limits
10 ... 110 °C
min. 10, max. 55 °C
See section 22
3
Room temperature influence
0 ... 99 / -99 ... 0
min. 0, max. -40
See section 23
4
Proportional band, Xp
1 ... 250 K
See section 26
5
Integration time constant, Tn
5 ... 999 sec.
See section 26
6
Running time of the motorized control
valve
5 ... 250 sec.
See section 26
7
Neutral zone, Nz
0 ... 9 K
See section 26
Section 17
Sections 18 & 19
Section 20
Your settings
0.6
0 K
18 °C
80 K
140 sec.
140 sec.
3 K
ECL Card settings
(circuit II)
A
Time and date
B
System information
C
System information,
circuit II
Setting ranges
Factory settings
Switching difference, stage I and II
1 ... 30 K
See section 27
1
Bivalent points, stage I and II
-50 ... 50 / -50 ... 50 °C
min. -50, max. 50 °C
See section 27
2
Flow temperature (S5), min. / max. limits
10 ... 110 °C
min. 10, max. 55 °C
See section 27
3
Operating hours counter and
cut-in commands, stage I
See section 27
4
Operating hours counter and
cut-in commands, stage II
See section 27
5
Temperature readouts, sensors S7
and S8
See section 27
6
Temperature readouts, sensors S9
and S10
See section 27
7
DHW switching difference
1 ... 30 K
See section 27
30b
Section 17
Sections 18 & 19
Section 27
Your settings