32d
Service parameter(s) 15-17
15 Adaptive function of room temperature
Circuit
Setting range
I
OFF / 1 ... 30
Controls how fast the room temperature adapts to the desired
room temperature.
The adaptive function will eliminate the difference
between the desired and the actual room
temperature. This is done by integrating the
difference and adjusting the desired flow
temperature.
OFF: The adaptive function is cancelled.
1:
The desired temperature is adapted quickly.
30:
The desired temperature is adapted slowly.
17 Influence on desired heat pump temperature
(temperature difference between sensors S3 and S5)
Circuit
Setting range
II
OFF / 1 ... 20 K
The desired flow temperature (at S5) in the heat pump circuit
can be influenced by the desired flow temperature in the mixing
circuit.
OFF: The desired flow temperature is controlled
directly by sensor S5.
1 ... 20:
The desired flow temperature in the heat
pump circuit is determined by the desired
temperature in the mixing circuit. The
desired temperature of the heat pump is
increased by the set value (system types
10.5, 10.6, 10.7, 10.8 and 10.9).
Temp.
Setting line 17
Desired
temp. S5
Desired
temp. S3
A temperature increase is only possible within the min. and max.
temperature range (section 27, line 2).
The grey
side of the
ECL Card
Factory setting
OFF
Factory setting
OFF
Time
Service parameter(s) 20-21
20 Optimization based on room / outdoor temperature
Circuit
Setting range
I
ON / OFF
The optimized start and stop time can be based on either room or
outdoor temperature.
ON: Optimization based on room temperature, if
measured.
OFF: Optimization based on outdoor
temperature. Use this setting if the room
temperature is not measured.
21 Total stop
Circuit
Setting range
I
ON / OFF
Decide whether you want a total stop during the setback
temperature period.
ON: The desired flow temperature is lowered
to 10 °C. The min. setting of the flow
temperature (line 2, section 22) is overruled.
Desired flow
temp. (°C)
10 °C
OFF: No total stop
Desired flow
temp. (°C)
10 °C
32e
Factory setting
OFF
Factory setting
OFF
Time
Time
The grey
side of the
ECL Card