Heating cut-out -
line 1
1
1
2
ON
ON
1
1
8
1
Limit for heating cut-out
Circuit
Setting range
I
10 ... 30 °C
Set the outdoor temperature limit at which you
want the heating system to stop.
The valve closes and after about 3 min. the heating
circulation pump stops.
The min. limitation set in line 2 will be ignored.
Temp.
Actual
outdoor temp.
18 °C
Heating
Heating OFF
This function can save energy by stopping the heating system
when the outdoor temperature gets above a set limit. The heating
system switches ON again when the outdoor temperature and
the accumulated outdoor temperature become lower than the set
limit.
The heating cut-out is only active when the controller mode is
scheduled operation. When the limit value is set to 30, there is no
heating cut-out.
The grey
side of the
ECL Card
2
Factory setting
18 °C
Accumulated
outdoor temp.
Heating
Time
Flow temperature limits -
line 2
1
1
2
ON
ON
2
Min. flow
1
0
temp.
Setting range
2
Flow temperature limits, min. and max.
Circuit
Setting range
I
10 ... 110 °C
The left end of the setting range blinks. Adjust the
min. limit of your system temperature.
Choose the max. limit. The right end of the setting
range blinks.
Adjust the max. limit.
During hours with low rate, the electric heater can heat the
system up to the max. flow temperature limit.
22
2
3
ON
Max. flow
5
5
temp.
Factory setting
min. 10, max. 55 °C
The grey
side of the
ECL Card