Reflex Winkelmann GmbH accepts no liability for any damage resulting from vicinity can occur. failure to observe the information in this operating manual. In addition to the requirements set out in this operating manual, national statutory regulations ...
"SV" safety valves of the vessel. Control unit The control unit comprises a "CO" compressor and the "Reflex Control Basic" controller. Via the primary vessel, the pressure is measured with the "PIS" pressure sensor and the water level with the "LIS" pressure load cell and the values then displayed in the controller display.
"LIS" pressure load cell for level sensing. Optional equipment and accessories • For make-up with water • Make-up without pump: – Solenoid “Fillvalve” with ball valve and Reflex Fillset for make- Primary vessel up with drinking water. • Make-up with pump: Note! –...
Ensure that pipes are connected from the device to the system without prerequisite for the making of warranty claims. them being stressed or strained. – Have the Reflex Customer Service carry out commissioning and • If necessary, provide support structures for the pipes or equipment. the annual maintenance.
Water-side connection Overflow solenoid valve, blue “PV” identification Level measurement, yellow “LIS” identification The connections of the Reflexomat Silent Compact are pre-fitted in the factory. Fitting the level sensor, see chapter 6.3.3 "Fitting the level sensor" on page 7 . 6.3.3...
4.6 "Optional equipment persons. and accessories" on page 5 . If you don't use a Reflex Fillset, you must use an "ST" • Ensure that installation work for the electric connection of the device is dirt trap with a mesh size ≥...
Note! Factory • For controlling pressurisation If required, please contact the Reflex Customer Service for the protocol in the overflow line. of the RS-485 interface, details of the connections and information about the accessories offered. 230 V output for water make-up.
Plug in the contact plug to provide power (230 V) to the controller. not yet switch to Automatic mode. You are now in Stop mode. The "Auto" LED on the operator panel has extinguished. 10 — English Reflexomat Silent Compact — 16.10.2020 - Rev. A...
The "CO" compressor and the "PV1" solenoid valve are regulated by the controller so that the pressure remains constant in a regulation range of ± 0.1 bar. • Faults are indicated and evaluated in the display. Reflexomat Silent Compact — 16.10.2020 - Rev. A English — 11...
Press "Menu" to display the first main menu option "Customer menu". returns the "Make-up cycles" fault message. 003 / 2 h 12 — English Reflexomat Silent Compact — 16.10.2020 - Rev. A...
Check set value in the Customer or Service menu. "Quit" • Pressure relief pipe not functioning. • Check functioning of the pressure relief pipe. • Dirt trap clogged. • Clean the dirt trap. 14 — English Reflexomat Silent Compact — 16.10.2020 - Rev. A...
16 . maintenance counter in the Customer menu. Note! Arrange for maintenance tasks must be carried out only by specialist personnel or Reflex Customer Service. Reflexomat Silent Compact — 16.10.2020 - Rev. A English — 15...
Note! The setting values for pressurisation, filling levels and make-up can be found in the chapter Default settings, see chapter 9.2.1 "Default settings" on page 13 . 16 — English Reflexomat Silent Compact — 16.10.2020 - Rev. A...
Prior to dismantling, block off all "water"-side connections to the device. Note! • De-pressurise the device by venting it. Clean all other installed dirt traps (in the Reflex Fillset, for example). Disconnect the system from the power supply and secure it against 10.4 Inspection unintended reactivation.
Page 18
The settings in the controller match the local conditions. Typ / Type: Fabr. Nr. / Serial-No. 18 — English Reflexomat Silent Compact — 16.10.2020 - Rev. A...