Controller; Operator Panel; Configuring Settings In The Controller - Reflex Reflexomat Silent Compact Operating Manual

Table of Contents

Advertisement

Controller

9
Controller
9.1

Operator panel

1
Error LED
The Error LED illuminates in the event of a fault
2
Display
3
Auto LED
The Auto LED illuminates green in Automatic mode
The Auto LED flashes green in Manual mode
The Auto LED is not illuminated when the system is stopped
4
OK
Confirm actions
5
Stop
For commissioning and entry of new values in the controller
6
"Back" to the previous menu
7
Manual
For tests and maintenance tasks
8
Auto
For continuous operation
9
"Forward" to the next menu
10
Menu
Call up the Customer menu
11
Quit
Acknowledge messages
Selecting and changing parameters
1.
Use "OK" (5) to select the parameter.
2.
Use the "▼" (7) or "▲" (9) arrow keys to change the parameter.
3.
Use "OK" (5) to confirm the parameter.
4.
Use the "▼" (7) or "▲" (9) arrow keys to switch to a different menu
option.
5.
Use "Quit" (11) to switch to a different menu level.
9.2

Configuring settings in the controller

You can configure the controller settings regardless of the currently selected and
active operating mode.
System-specific values can be corrected via the customer menu. In the course of
initial commissioning, the factory settings must first be adjusted for the system-
specific conditions.
Note!
For a description of the operation, see chapter 9.1 "Operator panel" on
page 12 .
All grey marked menu items must be reviewed during commissioning.
Press "Manual" to switch to manual operation.
Press "Menu" to display the first main menu option "Customer menu".
12 — English
Indication on the
display
Customer menu
Language
Time:
Date:
1 % / 1.7 bar
Null balancing?
0 % / 0 bar
Null balancing
successfully
concluded!
0 % / 0 bar
Cancel null
balancing?
No
Min.op.pressure
01.8 bar
Make-up
Make-up: ON
at: 08 %
Make-up: OFF
at: 12 %
Max. make-up time
010 min.
Max. make-up
cycles
003 / 2 h
Reflexomat Silent Compact — 16.10.2020 - Rev. A
Meaning
Switch to the next main menu option.
Standard software in various languages.
Adjust the "Hour", "Minute", and "Second" display when
each begins to flash.
This time is used for entries in the fault memory.
Adjust the "Day", "Month", and "Year" display when each
begins to flash.
This date is used for entries in the fault memory.
The controller checks whether the level sensor signal
matches the value entered for the "RG" primary vessel in
the controller, see chapter 7.3 "Modifying the controller's
start routine" on page 10 .
Note!
The "RG" primary vessel must be completely
empty.
One of the following messages appears on the display:
Null balancing concluded successfully
Confirm with the "▼" button.
Empty vessel and repeat the process
Confirm with "OK".
This message appears when null balancing has failed.
Select "Yes" or "No" on the display.
YES: The "RG" primary vessel is empty and the
device is installed as per the instructions. If null
balancing is still not possible, cancel with "Yes".
Contact your Reflex Customer Service.
NO: Check the prerequisites for the commissioning,
see chapter 7.1 "Checking the requirements for
commissioning" on page 9 .
The controller's start routine has been restarted.
Confirm the selection of "yes" or "no" with "OK".
Enter the value for the minimum operating pressure.
Note!
Calculation of minimum operating pressure, see
chapter 7.2 "Reflexomat switching points" on
page 10 .
Switch to the "Make-up" main menu.
Press "OK" to open the menu.
Use the "▼▲" buttons to open the sub-menu.
If the water content is below the specified vessel size,
add water, see chapter 7.3 "Modifying the controller's
start routine" on page 10 .
If an automatic make-up device (Fillcontrol for
example) is installed, make-up will be actuated
automatically; otherwise the make-up must be
manually activated.
Terminate the water make-up when the specified vessel
size is exceeded.
If an automatic make-up device is installed, make-
up will be shut off automatically; otherwise the
make-up must be manually deactivated.
If you have selected "No" for automatic make-up,
the system will not return any further queries
about the make-up.
Pre-selected time for a make-up cycle. Upon expiry of
this set time, the system interrupts the make-up and
returns the "Make-up time" fault message.
If the set number of make-up cycles is exceeded within
two hours, the system interrupts the make-up and
returns the "Make-up cycles" fault message.