Honeywell Fire-Lite Alarms MRP-2001 Instruction Manual page 15

Pre-action/deluge control panel
Table of Contents

Advertisement

Specifications
Special Application Resettable or Nonresettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA
Power-limited Circuitry
Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable power
Jumper pins 2 & 3 on JP31 for resettable power
Refer to the Device Compatibility Document for compatible listed devices
Special Application Primary ANN-BUS Power - TB3
Operating voltage: Nominal 24 VDC
Maximum Available Current: 500 mA
Power-limited circuit
Special Application Secondary ANN-BUS Power - ANN-SEC - TB1
Operating voltage: Nominal 24 VDC
Maximum Available Current: 500 mA
Power-limited circuit
The following figure illustrates the maximum current that is possible for each major panel output
circuit and the total current available from the FACP with the FLPS-7 power supply.
Special Application
Nonresettable or
Resettable Power
Special Application
Resettable Power
NAC #1
NAC #2
NAC #3
NAC #4
Primary
ANN-BUS
ANN-SEC
Option Card
MRP-2001 Series Manual — P/N 53040:H 1/26/2017
TB9
0.5 amp max
per circuit
0.5 amp max
per circuit
TB5
3.0 amps max
per circuit
3.0 amps max
per circuit
TB7
3.0 amps max
per circuit
3.0 amps max
per circuit
TB3
0.5 amp max
per circuit
TB1
0.5 amp max
per circuit
Figure 1.1 Current Availability
Standby
1.0 amp max
per panel
Refer to the battery calculations
section for additional information.
Standby
1.0 amp max
per panel
Product Description
Alarm
7.0 amps
max
per panel
15