Section 3: Programming; User Programming - Honeywell Fire-Lite Alarms MRP-2001 Instruction Manual

Pre-action/deluge control panel
Table of Contents

Advertisement

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
Program feature or
option
ANN-80 Lock Enable
Combo
Combo w/AutoResettable
Superv
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in
CAN/ULC-S527, Standard for Control Units for Fire Alarm Systems, certain programming features or options must be limited to
Program feature or
Permitted in ULC-S527?
option
Release Circuit Short
Supervision
Canadian Option

3.1 User Programming

The FACP is completely field programmable using the panel keypad and requires no special
software skills. While programming the FACP, the fire protection capabilities of the control panel
are enabled. Programming Mode times-out after 10 minutes of inactivity.
Program Templates have been provided to allow the panel to be quickly programmed with typical
job-site configurations. Refer to "Circuit Mapping and Cross-Zoning" on page 91 for an
explanation of mapping and cross-zoning and "FACP Configuration Templates" on page 96 for a
detailed description of each template.
Site-specific programming may be accomplished:
by Manual programming or editing, using the FACP keypad
The System All Normal screen will be displayed in a programmed system with no active alarms,
troubles or supervisories, as illustrated below:
48

Section 3: Programming

limited to specific values or not used at all as indicated below.
Permitted in UL 864? (Y/N)
Y
Y
Y
specific values or not used at all as indicated below.
(Y/N)
Y
Y
Refer to "Canadian Option" on page 66.
Possible settings
Lock Enable Yes
Lock Enable No
Refer to Lock Enable in "ANN-80
Options" on page 69
Refer to Table 3.1 on page 52.
Refer to Table 3.1 on page 52.
Possible settings
UNSUPV Shorts
SUPV Shorts
Refer to "Release Circuit 1 or Release
Circuit 2" on page 57.
ON
OFF
SYSTEM ALL NORMAL
10:00A 091814
MRP-2001 Series Manual — P/N 53040:H 1/26/2017
Settings permitted in UL 864
Lock Enable Yes
One Waterflow and one
Supervisory device
One Waterflow and one
Supervisory device
Settings permitted in
ULC-S527
SUPV Shorts