Valor L1 1600KN Installation Manual page 33

Table of Contents

Advertisement

Installation
Pressure Test Points
The minimum supply pressure is given in the section
"Specifi cations" on page 6.
All piping and connections must be tested for leaks
after installation or servicing. All leaks must be
corrected immediately.
When testing for leaks:
• Make sure that the appliance is turned off .
• Open the manual shut-off valve.
• Test for leaks by applying a liquid detergent or soap
solution to all joints. Bubbles forming indicate a gas
leak.
 Caution
Never use an open flame to check for leaks!
Correct any leak detected immediately.
The pressure test tapping locations are shown in
the fi gure at right. An internal regulator within the
valve controls the burner manifold pressure. The
correct pressure range is shown in the table in section
"Specifi cations" on page 6. The pressure check
should be made with the burner alight and at its
highest setting. See "Appendix A—Lighting Instructions"
on page 58 for full operating details.
Valve Inlet
Pressure
Manifold
Test
Pressure
Pressure Testing
Gas Supply
Manifold pressure
adjustment screw
located behind
plastic mushroom
cap.
33