SP2/SP4/SP8/SP8-X20 Manual
Warning high :- the %age humidity level at which it is high
Warning low :- the %age humidity level at which it is low
Critical low :- the %age humidity level at which it is critically low
Rearm :- Used to prevent the sensor from flickering between two states. For example if the "High
Warning" threshold for the temperature sensor is set to 80 degrees and the sensor were to vary
between 79 and 80 you could be faced with a very large number of emails, traps, and events
logged. The Rearm parameter prevents this by forcing the temperature to drop by the Rearm
before changing the state back to normal. In this example if the Rearm is set to 2 then, the sensor
would have to drop from 80 down to 77 before the status would change from that back to normal.
Reading offset :- This will adjust the reading by your offset amount.
In our example we have set the parameters as indicated in the screenshot above. Once you have
done this click on "save".
For information on setting up other sensor types please refer to the manual for your specific
sensor. This will give you guidance in setting up the parameters specific to your sensor.
Sensor Status Filters: - By clicking on the "Sensors Status Filters" button shown in the image
above on page #16, you can then adjust the continuous time the sensor is in a warning, error, or
normal state before the unit sends the alerts. This feature was added to eliminate false warnings.
Important Note: Sensor Status Not Changing – If after setting up your sensors and alert
thresholds in the sensorProbe units web UI, you don't see the sensor status changing, always
check the "Rearm" and the "Offset" settings as these will delay the sensors from changing to the
new status thresholds.
Important Note: Our units and sensors are fully SNMP compliant, so they can be integrated into
most any third party NMS (Network Management System) software. You will need our latest MIB
file and also our OID manual for this which both can be downloaded from our support portal using
these links:
http://www.akcp.in.th/downloads/Manuals/AKCP%20OID/akcp.mib
http://www.akcp.in.th/downloads/Manuals/AKCP%20OID/AKCP%20SNMP%20OID%20Manual.p
df
Updated until firmware 476
- 17 -