10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.1 EtherNet/IP
10.1.3 EtherNet/IP Electronic Data Sheet (EDS file)
10.1.4 EtherNet/IP register map
10.1.4.1 Input status (discrete inputs)
84
Each device in an EtherNet/IP network is associated with an Electronic Data
Sheet (EDS file), which describes the implementation of the product.
This file is used by the network configuration tool during network
configuration.
→
If necessary, the latest version of the EDS file for the
PXR-ECAM-IP can be downloaded here:
https://www.eaton.com/digitalnzm
There are seven different release types in the NZM digital circuit breaker
family. As a result, the devices access the registers differently, since not all
versions support all functions.
The release type -AX does not support a communication connection; register
access is therefore not possible.
→
The available functions overview, for each trip unit type, can be
found on → chapter 3, "Protection and measurement functions",
page 19.
The input status bits can be requested via object: 0xA2,
with attribute: 5 and Instance: 1.
The input status answer is a 4 bytes data type. The first 16 bits (1001 to
1016) indicate the current status, while the last 16 bits (1017 to 1032)
indicate whether the corresponding status is valid or supported by the
release unit.
Table 47: Input status - EtherNet/IP
Input
Description or value
1001
The breaker is in the closed position
1002
Unacknowledged trip condition
1003
Active or unacknowledged alarm
1004
0
1005
Maintenance mode is active
1006
Test mode is active
1007
0
1008
0
1009
0
1010
Overload mode is active
(an overload is present)
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Input
Description or value
1017
The breaker is in the closed position and
is valid
1018
Unacknowledged trip condition is valid
1019
Active or unacknowledged alarm is valid
1020
0
1021
Maintenance mode is active and valid
1022
Test mode is active and valid
1023
0
1024
0
1025
0
1026
Overload mode is active and valid
(an overload is present)