10.2.3.6 Date and time
10.2.3.7 Primary status codes
10 Industrial Ethernet Communication Adapter Modules (ECAM)
Table 73: Remote control - EtherCAT
Command
Definition
group
Reset
Reset the trip
Reset the min./max. values of the L-N voltages1)
Reset the min./max. values of the L-L voltages1)
Reset the peak power requirement1)
Reset all min./max. values
Reset the energy1)
Reset the power-up display
Maintenance
Activate the maintenance mode
mode
Deactivate the maintenance mode
The release supports the reading and writing of real-time clock information
by the external communication module EtherCAT.
Eight registers, starting with index number 215E, are reserved for this
purpose.
Table 74: Real-time clock - EtherCAT
Index [Hex]
Definition
215E
Month
215F
Day
2160
Year
2161
Day of the week
2162
Hour
2163
Minute
2164
Seconds
2165
1/100 of a second
Table 75: Primary status codes - EtherCAT
Code
Meaning
0x01
open
0x02
closed
0x03
tripped
0x04
Alarm active
0x0D
Threshold value active
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Bit
Byte 2
0
0
0
0
0
0
0
1
1
Data range
1 - 12
1 - 31
2000 - 2099
1 = Sunday
...
7 = Saturday
0 - 23
0 - 59
0 - 59
0 - 99
10.2 EtherCAT
Byte 1
Byte 0
0
2
1
15
1
14
0
4
1
4
0
8
0
3
0
8
0
9
129