10 Industrial Ethernet Communication Adapter Modules (ECAM)
The following instances are assigned to the data objects.
Table 53: Event summary - EtherNet/IP
Instance
Format
316
Encoded
317
Unsigned 32
318
Unsigned 32
319
Unsigned 32
320
Unsigned 32
321
Unsigned 32
322
Date/time
323
Encoded
324
B0
325
Encoded
Table 54: Historical trip / major alarm event - EtherNet/IP
Instance
Format
316
Encoded
317
Unsigned 32
318
Unsigned 32
319
Unsigned 32
320
Unsigned 32
321
Unsigned 32
322
Date/time
323
Encoded
324
Bit 15 - Bit 0
325
Bit 31 - Bit 16
326
Encoded
327
Unsigned 32
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
R/W
Description (historical event overview)
R/W
Event type: summary = 0x8EFF
R
Earliest event ID
R
Latest event ID
R/W
Requested event ID
R
Previous event ID
R
Next event ID
R
Date/time
R
Data format:
0x0000, 0x0001, 0x0004, 0x0005, 0x0005, 0x0006
R
Valid bit of the object
R
Cause of event:
00: boot process - time OK
01: download of the setpoint values
02: time has been adjusted
03: trip
04: alarm
05: test mode has been selected
06: exiting the test mode
08: boot process - no time
09: test completed
10: maintenance mode activated
11: maintenance mode deactivated
12: opened via the communication interface
13: closed via the communication interface
R/W
Description (historical event overview)
R/W
Event type:
Trip: 0x80FF
Alarm: 0x81FF
R
Earliest event ID
R
Latest event ID
R/W
Requested event ID
R
Previous event ID
R
Next event ID
R
Date/time
R
Data format:
Trip: 0x0004
Main alarm: 0x0005
R
Valid bits of the object
R
Valid bits of the object
R
Status reason (primary, secondary, reason)
R
I
(IA)
L1
10.1 EtherNet/IP