3 Protection and measurement functions

3.4 Power and energy measurements

3.4 Power and energy measurements
22
The following power and energy values can be measured.
Table 13: Power and energy measurements
1)
Measurement
Power measurement
Active power
Apparent power
Reactive power
Active power requirement
Apparent power requirement
Reactive power requirement
Active power requirement (peak)
Apparent power requirement (peak)
Reactive power demand (peak)
Power factor
Energy measurement
Active energy (forward)
Active energy (reverse)
Net active energy
Total active energy
Apparent energy
Reactive energy (forward)
Reactive energy (reverse)
Net reactive energy
Total reactive energy
1) Accuracy: Class 1 (derived from IEC61557-12)
The power and energy values are calculated and updated internally at a
frequency of 1 Hz.
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Unit of
Note
measure
kW
Updated after approximately 1 second
kVA
Updated after approximately 1 second
kvar
Updated after approximately 1 second
kW
Fixed window of 5 to 60 minutes
kVA
Fixed window of 5 to 60 minutes
kvar
Fixed window of 5 to 60 minutes
kW
Value is held until reset
kVA
Value is held until reset
kvar
Value is held until reset
Updated after approximately 1 second
kWh
From the source to the load
kWh
From the load to the source
kWh
"Active energy (forward)" - "active energy (reverse)"
kWh
"Active energy (forward)" + "active energy (reverse)"
kVAh
kvarh
From the source to the load
kvarh
From the load to the source
kvarh
"Reactive energy (forward)" - "reactive energy (reverse)"
kvarh
"Reactive energy (forward)" + "reactive energy (reverse)"