Page 3
Danger! Dangerous electrical voltage! Before commencing the installation • Disconnect the power supply of the device. • Wherever faults in the automation system may cause damage to persons or property, external measures must • Ensure that devices cannot be accidentally retriggered. be implemented to ensure a safe operating state in the •...
Standards, guidelines, approvals..........10 Design ..................11 Operator interface ................ 12 2.1.1 Rotary switch on the PXR10 and PXR20 trip units....... 12 2.1.2 LCD display on the PXR25 trip units ..........13 Micro-USB connection ..............15 LED Status indication ..............16 Trip reason indicator..............
Page 6
Interface module................41 Relay module ................43 Testing the trip unit and the circuit breaker ......47 Testing (remote) of the circuit-breaker via USB/PXPM ....48 Testing the ground-fault releases - primary injection ....48 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 7
Date and time................74 9.3.9 Internal diagnostics ..............75 9.3.10 Primary status codes..............76 9.3.11 Secondary status codes ............... 76 9.3.12 Reason codes................76 9.3.13 Device information ............... 77 9.3.14 Exception codes................78 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 8
Configuration of the Modbus parameters........133 10.3.2 IP configuration/DIP Switch Settings ........... 134 10.3.3 Profinet (GSDML file)..............135 10.3.4 Profinet register map ..............135 Troubleshooting................. 159 PXR25 Navigation menu ............161 Alphabetical index ..............165 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
0.1 List of revisions 0 About this manual This manual covers the PXR10, PXR20 and PXR25 electronic trip units of the NZM digital circuit breaker as well as the relevant accessories. The manual describes the various versions of the product series, as well as their installation and operation.
Zone selective interlocking → The abbreviation PXR: For the PXR10, PXR20 and PXR25 versions, the abbreviation PXR is used if a statement applies equally to all three. The symbols used in this manual have the following meanings: ▶ indicates an action to be taken.
Indicates a potentially hazardous situation that may result in death or serious injury DANGER Indicates an imminently hazardous situation that will result in death or serious injury 0.3.3 Tips → Indicates useful tips. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
White paper on live electrical circuits” “Improved lifecycle management White paper thanks to digital circuit protection” “xSpider” Software www.eaton.com/xspider (graphical design system for the planning of low-voltage networks) “Power Xpert Protection Manager” Software www.eaton.com/PXPM PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
NZM4 series) consists of current sensors and a trip actuator in conjunction with the PXR (Power Xpert Release) electronic trip. The electronic trip units PXR10, PXR20 and PXR25 in particular ensure the protection function of the circuit breaker. In addition to its main function (= protection), the PXR electronic trip unit makes it possible •...
The PXR trip units are also certified for use in the NZM...NA series circuit breakers by Underwriters Laboratories Inc. (UL) and the Canadian Standards Association (CSA). → Further information on the NZM digital circuit breakers can be found on the Eaton website: www.eaton.com/digitalNZM PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
NZM circuit breaker with PXR trip unit Please note: The operator interfaces of the trip units differ from one another: The PXR10 and PXR20 versions are fitted with rotary switches, while on the PXR25 version, an LCD display is used for indicating and adjusting the settings.
2 Design 2.1 Operator interface 2.1 Operator interface 2.1.1 Rotary switch on the PXR10 and PXR20 trip units Depending on the type of trip unit, there are up to seven rotary switches at the front of the unit. 6.5 7 7.5 11 12 13 0.2 0.3...
The following languages are pre-installed: • English • German • French • Italian • Polish • Dutch • Norwegian • Swedish → Additional language packs can be installed via the Power Xpert Protection Manager configuration software. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 18
The status LED indicates if the trip unit is ready for operation. During normal operation, this LED will flash green. → Also see → chapter 12, “PXR25 Navigation menu”, page 161 for a graphical representation of the navigation menu. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Standard Micro-USB on USB-A cable Temporary connection for using the Power Xpert Protection Manager Standard Micro-USB power bank To establish a temporary connection for supplying power to the trip unit if the unit is not self-supplying. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
This therefore does not constitute a malfunction. The Status LED will flash again if the auxiliary power supply is activated, or if the load on the circuit breaker rises to a level greater than 15 %. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
2.4 Trip reason indicator 2.4 Trip reason indicator PXR10 The PXR10 trip units are not equipped with any indicators. PXR20 The PXR20 trip units are equipped with up to four trip-reason indicators at the front. These indicators are marked LONG, SHORT, INST and GND.
2.5 Overload indicator 2.5 Overload indicator PXR10, PXR20 The PXR10 and PXR20 trip units are equipped with an orange overload LED for load and overload warnings, which are triggered at 85 % (LED on) and 105 % (LED flashing) of I , respectively.
Page 24
Eaton publication “Setting-specific representation of tripping characteristics and competent assessment of their interaction”, which is available for download on the Eaton website: www.eaton.eu/ecm/groups/public/@pub/@europe/@electrical/documents/content/pct_998455_de.pdf → The xSpider software is available on the Eaton website at www.xspider.eaton.eu PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Maximum VL1-N, VL2-N, VL3-N Group values are held until reset 1) PXR10 / PXR20: Accuracy of current measurement: 5 % valid for 40 % to 100 % of I PXR25: Accuracy of measurement: 0.5 % Current measurement: valid for 10 % to 120 % of I at 25 °C (77 °F)
Total reactive energy kvarh “Reactive energy (forward)” + “reactive energy (reverse)” 1) Accuracy: Class 1 (derived from IEC61557-12) The power and energy values are calculated and updated internally at a frequency of 1 Hz. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
3.5 Time/current characteristics 3.5 Time/current characteristics The time/current characteristics of the PXR trip units on the NZM circuit breakers can be found in Eaton’s xSpider software via the link listed below. → The xSpider software is available on the Eaton website at: www.xspider.eaton.eu...
Page 28
3 Protection and measurement functions 3.6 Voltage tap of the neutral conductor on the PXR25 L1 L2 L3 Figure 6: Connecting the N conductor on the NZM4 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Ground-fault trip I • Ground-fault delay time t The settings can be adjusted using the rotary switches (on the PXR10 and PXR20 trip units) or the display (on the PXR25 trip unit) at the front of the trip unit. Additional options can be selected via the display (on the PXR25 trip unit only), the navigation buttons, the Power Xpert Protection Manager configuration software (on all PXR variants) or the communication link.
This function enables the circuit breaker to protect both downstream cables (outgoing cables) and equipment as well as its own integrity against excessive heating in the event of repeated overcurrents. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
A ground-fault alarm ensures early warning in the event of a ground fault, while a ground-fault trip provides protection in this case. The following three modes of operation can be selected. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 32
If a 3-pole circuit breaker is used in a neutral network, the neutral current will not be detected. In this case, a ground-fault trip may occur if the threshold values of the ground-fault release are exceeded. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
4.8 Digital bypass Should the main processor malfunction, the secondary processor will take over at 1.2 x I If the value exceeds 1.2 x I , the circuit breaker will trip immediately. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
4.9 Maintenance mode (ARMS) 4.9 Maintenance mode (ARMS) The PXR25 trip units support Eaton’s Arc Flash Reduction Maintenance System™ (ARMS). This is also known as the maintenance mode. If enabled, the trip unit will trip the circuit breaker with no intentional delay whenever the configured threshold value is exceeded.
This restraining signal will cause all upstream circuit breakers to continue operating with their own coordination delays, to ensure that the supply is only interrupted locally. Figure 8: ZSI circuits PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Zone Out (Z • Zone Common (Z These signals are compatible with all Eaton circuit breakers that have the ZSI function. An output signal will be transmitted each time the ground-fault threshold or the short-time delay threshold is exceeded. This provides maximum selectivity for coordination with larger upstream circuit breakers.
Page 38
L2-L3 • (VCA) L3-L1 • (VAN) L1-N • (VBN) L2-N • (VCN) L3-N 6 cycles (384 data points) → To use event logging in all operating states, an external power supply is required. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
To use the residual-life indicator in all operating states, an external power supply is required. → If you have any questions or feedback regarding the residual-life indicator, please contact your local Eaton technical support. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
In the case of the PXR20 trip units, an interface module can be optionally installed. → It is not possible to use an interface module with the PXR10 trip units. 5.1 Integrated Modbus communication module An integrated Modbus communication module is available as an optional accessory for the PXR20 and PXR25 trip units.
The CAM modules are equipped with two relay outputs and three digital inputs. The outputs and inputs can be configured for various functions. → The PXR-XCAM-NZMCABLE cable is not included in the delivery of the CAM... and has to be ordered separately. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
In such critical applications, the immunity of switch gear and control gear can be further improved. EATON recommends in such critical applications the use of a snap-on ferrite (e.g. type WE 74271132 by Würth Electronic). The ferrite should be installed on the external 24 V DC power line in close proximity to the circuit-breaker.
Should this power supply be interrupted, the real-time clock has to be set up again. 6.4 Power Xpert Protection Manager (PXPM) Eaton’s free Power Xpert Protection Manager (PXPM) is a Microsoft® Windows-based software for configuring, controlling and testing the Eaton PXR trip units.
ARMS remote switching (only on the NZM3 and the NZM4) g ZSI connection h VN connection for the voltage tap of the neutral conductor (only on the NZM4) i Status indication of the remote operator PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 46
PXR25”, page 23. The PXR20 trip units do not have a voltage tap for the neutral conductor, as they do not measure the voltage. Figure 11: Removing the interface module PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
For example, it is possible to switch the remote operator of the circuit breaker, or a downstream contactor can be “dropped” in order to prevent the circuit breaker from tripping in the event of a slight overload. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 48
50 % and 120 % of I The relay will drop out again with a hysteresis of 5 % below the set threshold value. Default settings: 105 % PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 49
The relay will respond if the circuit breaker is in the switch (HIA) (1 -> 0): status - device has been reset “tripped” contactor state. Once this is no longer the case, the relay will drop out. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 50
“close relay” via the communication interface. The relay will drop out if it has received the command “open relay” via the communication interface, or if the external power supply of the breaker has been interrupted. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
A password is required to prevent any unauthorized access that may cause the circuit breaker to trip. → Password: The default password is 0000. This can be changed in the device settings. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Such testing must be performed in accordance with the applicable local and national regulations. You can also use the Power Xpert Protection Manager software to save and print a copy of the circuit-breaker settings for your testing records. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Modbus RTU input cable b Modbus RTU output cable c Bus termination resistor (for the final node) d Modbus RTU-compatible cable: triple wire; two twisted signal wires; one shielded COM wire e HF-compatible functional grounding PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
(voltage, power, energy, and the power factor) can be used in the real-time data. • Release type -PX...-TAZ supports the maintenance mode. For this type, the maintenance mode setpoints can be accessed in group 0 and in the “Remote Control” group. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
“data cracks”. Any attempt to access a partial data object will return the exception code 04. → For more information on the exception codes, see → section 9.3.14, “Exception codes”, page 78. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 57
Peak reactive power demand 404799 406335 12BE 18BE Peak apparent power demand 404845 406381 12EC 18EC Active power demand 404847 406383 12EE 18EE Reactive power demand 404849 406385 12F0 18F0 Apparent power demand PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 58
404975 406511 136E 196E Counter - trips total – 404977 406513 1370 1970 Counter - test mode tripping – 404979 406515 1372 1972 Counter - number of openings via the – communication interface PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 59
Conversion formula: Residual life expressed as a percentage = 100 - (point value / 100) Power objects are presented as fixed-point values in either the two-register fixed-point data format or the four-register coding format. The two-register format is displayed in kilowatt hours. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 60
Byte 4 of the mantissa Energy register 3 a = technical unit b = mantissa factor The energy value (four-register energy value) is calculated as follows: Energy = 2 x 48-bit energy value x 10 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 63
Bit 3: RelaySel: with relay module = 1 Bit 4: ZSISel: with zone selectivity = 1 Bit 12: NZM_ACB_Sel: degree of protection NZM = 1, IZMX = 0 Bit 13: IECSel: Standard IEC = 1, UL = 0 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 64
The low byte can be configured and is used to indicate the maintenance mode settings via the communication port (e.g. Modbus, CAM or USB). The respective protection settings may vary according to the size, type and rated operational current of the release. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 65
Bit 3: RelaySel: with relay module = 1 Bit 4: ZSISel: with zone selectivity = 1 Bit 12: NZM_ACB_Sel: degree of protection 0: IZMX 1: NZM Bit 13: IECSel: 0: UL 1: Standard IEC PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 66
(in increments of 1 (1 A)) Caution: The value range depends on the type: (e.g. a 250-A switch can be set in the range from 40 % to 100 % of I (value range: 100 - 250) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 67
85: 8.5 90: 9.0 95: 9.5 100: 10.0 The following applies to the NZM PXR25: The value range [20 - 100] corresponds to 2 to 10, in increments of 0.1 (1 for values) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 68
Settings - functioning of Encoded Type of ground-fault protection – the ground-fault protection 0: trip 1: alarm 2: OFF 403018 0x0001 ground-fault release - Encoded ground-fault release - waveform: – waveform 0: flat 1: I PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 69
Recommended for repetitive testing only. Among other things, the thermal memory protects the switch against overheating during repeated overloads. Must be reactivated after testing! 0: switched off 1: switched on PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
The number of valid bit registers is calculated as: (number of data objects - 1)/16 The following registers are assigned to the data objects. Any request outside the range of the register address will return the exception code 02. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 73
Main alarm: 0x0005 408213 Bit 15 - Bit 0 Validity bits of the object – 408214 Bit 31 - Bit 16 Validity bits of the object – 408215 Encoded Status reason (primary, secondary, reason) – PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 74
Previous event ID 408202 Signed 32 Next event ID 408204 Date/time Date/time 408212 Encoded Data format Small alarm: 0x0006 408213 Bit 0 Valid bits of the object 408214 Encoded Status reason (primary, secondary, reason code) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
9.3 Modbus register map 9.3.5 Block of registers The data object registers of an Eaton product can be rearranged by setting up a block of registers based on the register column in → table 26, page 61. The block of registers is stored in the non-volatile memory.
0x6300) are configured via the write function codes 06 or 16. In order to support Modbus masters that can only access register 9999, some Eaton registers that were originally assigned to registers above 9999 have been granted double access, both to the original register (to ensure compatibility) and to a new assigned register below 9999.
If the “slave action code” and the associated ones’ complement command are invalid, the release will return the exception code 03. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
The trip unit does not support this query or only part of a register is used in the query. ACK = acknowledged The trip unit is unable to execute the current request at this time. NAK = not acknowledged The trip unit is unable to execute the request. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Figure 16: Ethernet communication adapter modules power supply wiring a 24 V DC terminal (±10 %) The Modbus cable, which is connected to the ECAM, must comply with the specifications on → page 49 of this manual. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 84
Not used Ground Not available Output for external bus termination Not available Not used NZM Line B NZM Line A Connector Shield Functional earth (braided shield) Figure 18: Sub DB9 Male connector wiring PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 85
Function ① Indicates power presence ② Gateway Application ③ MRTU Modbus RTU Activity ④ – Not used ⑤ Network Status ⑥ Module Status ⑦ Link Activity Port 1 ⑧ Link Activity Port 2 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
After a power-cycle, meaning the switch off and then on of the module, the PXR-ECAM-IP does not save configured values but returns them to default values. The Modbus communication parameters of the NZM breaker (Modbus RTU slave) cannot be configured via Ethernet communication adapter module (ECAM). PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
If the DIP switches are set in the range from 1 to 254, the IP address settings of the device are determined by the switches: IP address: 192.168.1.<DIP Switch Setting> Subnet mask: 255.255.255.0 Default Gateway: 192.168.1.1 Invalid Setting. Device will not start-up properly. PWR and GW are flashing red. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
1022 Test mode is active and valid 1007 1023 1008 1024 1009 1025 1010 Overload mode is active 1026 Overload mode is active and valid (an overload is present) (an overload is present) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 89
Energy objects can only be obtained in fixed-point format. Registers for which the IEEE floating-point value is not specified are only supported in fixed-point format (FP). PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 90
Active energy (forward) – Active energy (reverse) – Active energy combined (= forward + reverse) – Apparent energy Peak reactive power demand Peak apparent power demand Active power demand Reactive power demand Apparent power demand PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 91
Counter - test mode tripping – Counter - number of openings via the communica- – tion interface Counter - external actuation – Time of last actuation – – (year, month, day, hour, minute, second) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 92
3) 0 points ≙ 100 % residual life 10.000 points ≙ 0 % residual life Conversion formula: Residual life expressed as a percentage = 100 - (point value / 100) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 93
For trip units that support settings, the settings of groups 0, 1 and 2 should be written one after the other. The setting groups are assigned as follows: • Group 0: System group • Group 1: Protective group • Group 2: Modbus group PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 94
Rated current Rated current communication address Frame size ● ● ● ● ● ● Trip type - part 1 ● ● ● ● ● ● Figure 21: Reading from setting registers – EtherNet/IP PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 96
Bit 3: RelaySel: with relay module = 1 Bit 4: ZSISel: with zone selectivity = 1 Bit 12: NZM_ACB_Sel: degree of protection 0: IZMX 1: NZM Bit 13: IECSel: 0: UL 1: Standard IEC PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 97
The low byte can be configured and is used to indicate the maintenance mode settings via the communication port. The respective protection settings may vary according to the size, type and rated operational current of the release. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 98
Recommended for repetitive testing only. Among other things, the thermal memory protects the switch against overheating during repeated overloads. Reactivate the thermal memory after testing: 0: switched off 1: switched on PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 99
140: 14 160: 16 180: 18 200: 20 32767: ∞ (overload protection deactivated) Load alarm 1 Unsigned Load alarm 1 level (AL1 = n % x I 50 - 120 (in increments of 1) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 100
50: 500 75: 750 100: 1000 The following applies to the NZM PXR25: The value range [0 - 100] corresponds to 0 to 1,000 ms, respectively, in increments of 0.1 (10 for values) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 101
40: 0.4 60: 0.6 80: 0.8 100: 1.0 The following applies to the NZM PXR25: The value range [20 - 100] corresponds to 0.2 to 1.0, in increments of 0.1 (10 for values) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 102
If the ground-fault protection function is set to groundfault “trip” (see register 403017), a pre-alarm can also release be set. = x % x I pre-alarm 50 - 100 (in increments of 5 %) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 104
1 for the second data object, bit 2 for the third data object, and so forth. The number of valid bit registers is calculated as: (number of data objects - 1) / 16 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 105
Main alarm: 0x0005 Bit 15 - Bit 0 Valid bits of the object – Bit 31 - Bit 16 Valid bits of the object – Encoded Status reason (primary, secondary, reason) – Unsigned 32 (IA) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 106
Requested event ID Signed 32 Previous event ID Signed 32 Next event ID Date/time Date/time Encoded Data format: Small alarm: 0x0006 Bit 0 Valid bits of the object Encoded Status reason (primary, secondary, reason code) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 107
ECAM from the controller via a dedicated industrial protocol object (via object: 0xA2, with attribute: 5 and instance: 410). → For more information on the exception codes, see → section 10.1.4.11, “Exception codes”, page 107. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 108
2000 - 2099 Day of the week 1 = Sunday … 7 = Saturday Hour 0 - 23 Minute 0 - 59 Seconds 0 - 59 1/100 of a second 0 - 99 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 109
Diagnostic warning #2 (configuration read error) 0x003D Overload 0x003E Short-time delay 0x0049 Phase currents are close to the threshold value, load alarm 0x004C Override 0x004D Setpoint error 0x004E Overtemperature 0x0050 Overload (neutral conductor) 0x0054 Ground fault 0x0071 Calibration PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 110
UL / IEC: 0x03 Poles 16-bit 3-pole / 4-pole Product ID Bitmap 32-bit ppppppvvvvdddddd Division code (dddddd) 06 (0x06) Product code (pppppp): 2: NZM2 PXR 3: NZM3 PXR 4: NZM4 PXR Comm version (vvvv) 0 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 111
No error Timeout error occurred Illegal function exception Illegal data address Illegal data value Slave device failure Slave acknowledge Slave device busy Memory parity error ECAM path unavailable ECAM target device failed to respond PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
This section details the data and functions available for the Digital NZM with PXR20 or PXR25 trip units via the PXR-ECAM-ECT register map. Depending upon trip unit capabilities, a large number of features are accessible through the registers as following described. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Information file (an ESI file), which describes the implementation of the product. This file is used by the network configuration tool during network configuration. → If necessary, the latest version of the ESI file for the PXR-ECAM-ECT can be downloaded here: https://www.eaton.com/digitalnzm PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Overload mode is active and valid (an overload is present) (an overload is present) 1011 Zone selectivity (ZSI) is active 1027 Zone selectivity (ZSI) is active and valid 1012 1028 1013 1029 1014 1030 1015 1031 1016 1032 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 115
– 2053 20D1 Frequency – 20D2 Active energy (forward) – 20D3 Active energy (reverse) – 20D4 Active energy combined (= forward + reverse) – 20D5 Apparent energy kVAh – 20D6 Active energy (forward) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 117
3) 0 points ≙ 100 % residual life 10.000 points ≙ 0 % residual life Conversion formula: Residual life expressed as a percentage = 100 - (point value / 100) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 118
For trip units that support settings, the settings of groups 0, 1 and 2 should be written one after the other. The setting groups are assigned as follows: • Group 0: System group • Group 1: Protective group • Group 2: Modbus group PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 119
Rated current communication address 2005 Frame size ● ● ● ● ● ● 2006 Trip type - part 1 ● ● ● ● ● ● Figure 23: Reading from setting registers - EtherCAT PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 121
1: on remote control 2009 2 - 0 0x0007 Maintenance Encoded 1: 2.5 x I mode: Trip setting 2: 4 x I 3: 6 x I 4: 8 x I 5: 10 x I PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 122
The low byte can be configured and is used to indicate the maintenance mode settings via the communication port. The respective protection settings may vary according to the size, type and rated operational current of the release. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 123
Recommended for repetitive tion) testing only. Among other things, the thermal memory protects the switch against overheating during repeated overloads. Reactivate the thermal memory after testing: 0: switched off 1: switched on PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 124
160: 16 180: 18 200: 20 32767: ∞ (overload protection deactivated) 200D Load alarm 1 Unsigned Load alarm 1 level (AL1 = n % x I 50 - 120 (in increments of 1) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 125
50: 500 75: 750 100: 1000 The following applies to the NZM PXR25: The value range [0 - 100] corresponds to 0 to 1,000 ms, respectively, in increments of 0.1 (10 for values) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 126
NZM PXR20: 20: 0.2 30: 0.3 40: 0.4 60: 0.6 80: 0.8 100: 1.0 100: 1000 The value range [20 - 100] corresponds to 0.2 to 1.0, in increments of 0.1 (10 for values) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 127
If the ground-fault protection function is set to groundfault “trip” (see register 403017), a pre-alarm can also release be set. (GF = x % x I ) 50 - 100 (in incre- pre-alarm ments of 5 %) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 129
1 for the second data object, bit 2 for the third data object, and so forth. The number of valid bit registers is calculated as: (number of data objects - 1)/16. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 130
0x0005 2144 Bit 15 – Bit 0 Valid bits of the object – 2145 Bit 31 – Bit 16 Valid bits of the object – 2146 Encoded Status reason (primary, secondary, reason) – PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 131
Previous event ID 2141 Signed 32 Next event ID 2142 Date/time Date/time 2143 Encoded Data format: Small alarm: 0x0006 2144 Bit 0 Valid bits of the object 2145 Encoded Status reason (primary, secondary, reason code) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 132
Modbus communication status of the ECAM from the controller via a dedicated industrial protocol object (via sub index: 0 and index 2167). → For more information on the exception codes, see → section 10.2.3.11, “Exception codes”, page 132. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 133
1/100 of a second 0 - 99 10.2.3.7 Primary status codes Table 75: Primary status codes - EtherCAT Code Meaning 0x01 open 0x02 closed 0x03 tripped 0x04 Alarm active 0x0D Threshold value active PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 134
0x0054 Ground fault 0x0071 Calibration 0x0088 Real-time clock 0x0099 Maintenance mode 0x009A Fault in the breaker mechanism 0x07FC Digital bypass 0x07FD Non-volatile memory failure 0x07FE Watchdog fault 0x07FF Motor alarm or motor tripping PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 135
2035 Poles 16-bit 3-pole / 4-pole 2037 Product ID Bitmap 32-bit ppppppvvvvdddddd Division code (dddddd) 06 (0x06) Product code (pppppp): 2: NZM2 PXR 3: NZM3 PXR 4: NZM4 PXR Comm version (vvvv) 0 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
This section details the data and functions available for the Digital NZM with PXR20 or PXR25 trip units via the PXR-ECAM-PNET register map. Depending upon trip unit capabilities, a large number of features are accessible through the registers as following described. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
After a power-cycle, meaning the switch off the trip unit, the PXR-ECAM- PNET does not save configured values but returns them to default values. The Modbus communication parameters of the NZM breaker (Modbus RTU slave) cannot be configured via Ethernet communication adapter module (ECAM). PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
If the DIP switches are set in the range from 1 to 254, the IP address settings of the device are determined by the switches: IP address: 192.168.1.<DIP Switch Setting> Subnet mask: 255.255.255.0 Default Gateway: 192.168.1.1 Invalid Setting. Device will not start-up properly. PWR and GW are flashing red. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 140
Overload mode is active 1026 Overload mode is active and valid (an overload is present) (an overload is present) 1011 Zone selectivity (ZSI) is active 1027 Zone selectivity (ZSI) is active and valid 1012 1028 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 141
IL3 (IC) (IG) ( IN) (VAB) L1-L2 (VBC) L2-L3 (VCA) L3-L1 (VAN) L1-N (VBN) L2-N (VCN) L3-N Active 3-phase power Reactive 3-phase power Apparent 3-phase power Power factor Frequency Peak active power demand PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 142
Minimum value - U (VAN) L1-N Maximum value - U (VAN) L1-N Minimum value - U (VAN) L2-N Maximum value - U (VAN) L2-N Minimum value - U (VAN) L3-N Maximum value - U (VAN) L3-N PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 143
3) 0 points ≙ 100 % residual life 10.000 points ≙ 0 % residual life Conversion formula: Residual life expressed as a percentage = 100 - (point value / 100) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 144
For trip units that support settings, the settings of groups 0, 1 and 2 should be written one after the other. The setting groups are assigned as follows: • Group 0: System group • Group 1: Protective group • Group 2: Modbus group PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 145
Rated current Rated current communication address Frame size ● ● ● ● ● ● Trip type - part 1 ● ● ● ● ● ● Figure 26: Reading from setting registers - Profinet PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 147
1: on control 2 - 0 0x0007 Maintenance Encoded 1: 2.5 x I mode: Trip setting 2: 4 x I 3: 6 xI 4: 8 x I 5: 10 x I PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 148
The low byte can be configured and is used to indicate the maintenance mode settings via the communication port. The respective protection settings may vary according to the size, type and rated operational current of the release. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 149
Recommended for repetitive tion) testing only. Among other things, the thermal memory protects the switch against overheating during repeated overloads. Reactivate the thermal memory after testing: 0: switched off 1: switched on PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 150
140: 14 160: 16 180: 18 200: 20 32767: ∞ (overload protection deactivated) Load alarm 1 Unsigned Load alarm 1 level (AL1 = n % x I 50 - 120 (in increments of 1) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 151
50: 500 75: 750 100: 1000 The following applies to the NZM PXR25: The value range [0 - 100] corresponds to 0 to 1,000 ms, respectively, in increments of 0.1 (10 for values) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 152
NZM PXR25: R/W NZM PXR20: 20: 0.2 30: 0.3 40: 0.4 60: 0.6 80: 0.8 100: 1.0 The value range [20 - 100] corresponds to 0.2 to 1.0, in increments of 0.1 (10 for values) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 153
If the ground-fault protection function is set to groundfault “trip” (see register 403017), a pre-alarm can also release be set. = x % x I pre-alarm 50 - 100 (in increments of 5 %) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 155
1 for the second data object, bit 2 for the third data object, and so forth. The number of valid bit registers is calculated as. (number of data objects - 1)/16 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 156
Trip: 0x0004 Main alarm: 0x0005 Bit 15 - Bit 0 Valid bits of the object – Bit 31 - Bit 16 Valid bits of the object – Encoded Status reason – (primary, secondary, reason) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 157
Requested event ID Signed 32 Previous event ID Signed 32 Next event ID Date/time Date/time Encoded Data format: Small alarm: 0x0006 Bit 0 Valid bits of the object Encoded Status reason (primary, secondary, reason code) PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 158
Modbus communication status of the ECAM from the controller via a dedicated industrial protocol object (via API 0 and index 167). → For more information on the exception codes, see → section 10.3.4.11, “Exception codes”, page 159. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 159
2000 - 2099 Day of the week 1 = Sunday … 7 = Saturday Hour 0 - 23 Minute 0 - 59 Seconds 0 - 59 1/100 of a second 0 - 99 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 160
Diagnostic warning #2 (configuration read error) 0x003D Overload 0x003E Short-time delay 0x0049 Phase currents are close to the threshold value, load alarm 0x004C Override 0x004D Setpoint error 0x004E Overtemperature 0x0050 Overload (neutral conductor) 0x0054 Ground fault 0x0071 Calibration PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 161
16 characters Sample version version 1 01.02.0033 Firmware ASCII 16 characters Sample version version 2 01.02.0033 USB version ASCII 16 characters Sample version 01.02.0033 Release 16-bit PXR10: 0x02 family PXR20: 0x01 PXR25: 0x01 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 162
UL / IEC: 0x03 Poles 16-bit 3-pole / 4-pole Product ID Bitmap 32-bit ppppppvvvvdddddd Division code (dddddd) 06 (0x06) Product code (pppppp): 2: NZM2 PXR 3: NZM3 PXR 4: NZM4 PXR Comm version (vvvv) 0 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
LCD display. The status LED is The circuit breaker locking mechanism is not closing Contact your Eaton representative for manufacturer support. permanently red or flashes properly. red. Internal memory issue. Contact your Eaton representative for manufacturer support.
Page 167
< Main menu Summary Events Trip Alarm Events Time change Main menu Diagnostic Diagnostic Settings < Main menu Summary Diagnostic Short circuit Overload Diagnostic Operation Runtime Figure 28: Menu items “measurement data”, “events” and “diagnostics”. PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 168
Settings Protection settings Protection settings Unit settings < Settings Long delay Protection settings Short delay Instantaneous Protection settings Ground fault ARMS Protection settings Thermal memory Protection settings Neutral Figure 29: Menu item “settings” PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Time Power setup Power setup < Unit settings Power feed Power setup Sign convention Power window Power setup Power demand interval Unit settings Relay #1 Relay #2 Figure 30: Menu item “device settings” PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...
Page 170
12 PXR25 Navigation menu PXR Electronic trip unit 01/21 MN012005EN www.eaton.com...