10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
Index
Bit
Mask
[Hex]
field
field
2009
0
0x0001
200A
0 - 1
0x0003
200B
200C
200D
120
Setpoint name
R/W
ZSI
R/W
Overload release -
R/W
waveform
Settings - release
R/W
(I
)
r
Settings - over-
R/W
load delay time (t
)
r
Load alarm 1
R/W
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Format
Description or value
Encoded
ZSI, zone-selectivity:
If enabled for releases with ground-fault protec-
tion, ZSI is implemented for both the short-time
delayed short-circuit release and for ground-fault
protection. If enabled for releases without
groundfault protection, ZSI is only implemented
for the short-time delayed short-circuit release.
0: switched off
1: switched on
Encoded
Waveform of the overload release
2
2: I
t (default setting)
Unsigned
Settings – overload (I
NZM PXR20: R
NZM PXR25: R/W
NZM PXR20:
40: 0.4
45: 0.45
50: 0.5
55: 0.55
60: 0.6
65: 0.65
70: 0.7
75: 0.75
80: 0.8
85: 0.85
90: 0.9
95: 0.95
100: 1.0
The following applies to the NZM PXR25:
General value range: 20 - 1600 (in increments of
1 (1 A))
Caution:
The value range depends on the type:
(e.g. a 250-A switch can be set in the range from
40 % to 100 % of I
Unsigned
Settings - overload delay time (t
NZM PXR20: R
NZM PXR25: R/W
NZM PXR20:
20: 2
40: 4
50: 5
60: 6
70: 7
80: 8
100: 10
120: 12
140: 14
160: 16
180: 18
200: 20
32767: ∞ (overload protection deactivated)
Unsigned
Load alarm 1 level (AL1 = n % x I
50 - 120 (in increments of 1)
= x * I
):
r
n
(value range: 100 - 250)
n
= x [s])
r
):
r
Unit
s
%

Hide quick links:

Advertisement