Eaton PXR10 Manual page 38

Electronic trip unit power xpert release for nzm circuit breakers
Hide thumbs Also See for PXR10:
Table of Contents

Advertisement

4 Protection settings
4.11 Event logging and waveform capture
34
Table 16: Event codes
Event code and time stamp
Alarm snapshot or
trip-snapshot
User waveform or
alarm waveform
Trip waveform
To use event logging in all operating states, an external power
supply is required.
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Logged event
• Current:
I
(IA)
L1
I
(IB)
L2
I
(IC)
L3
I
(IG)
G
I
(IN)
N
• Voltage (only on the PXR25):
U
(VAB)
L1-L2
U
(VBC)
L2-L3
U
(VCA)
L3-L1
U
(VAN)
L1-N
U
(VBN)
L2-N
U
(VCN)
L3-N
• Power: W, var, VA (only on the PXR25)
• Energy: Wh, Varh, VAh (only on the PXR25)
• Frequency
• Power factor
• Operations counter
Waveform of:
I
(IA)
L1
I
(IB)
L2
I
(IC)
L3
I
(IG)
G
I
(IN)
N
Waveform (only on the PXR25) of:
U
(VAB)
L1-L2
U
(VBC)
L2-L3
U
(VCA)
L3-L1
U
(VAN)
L1-N
U
(VBN)
L2-N
U
(VCN)
L3-N
1 cycle (64 data points)
Waveform of:
I
(IA)
L1
I
(IB)
L2
I
(IC)
L3
I
(IG)
G
I
(IN)
N
Waveform (only on the PXR25) of:
U
(VAB)
L1-L2
U
(VBC)
L2-L3
U
(VCA)
L3-L1
U
(VAN)
L1-N
U
(VBN)
L2-N
U
(VCN)
L3-N
6 cycles (384 data points)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pxr20Pxr25