10.2.3.2 Real-time data object register
10 Industrial Ethernet Communication Adapter Modules (ECAM)
Data that is subject to real-time changes, such as current, voltage and
energy, can be requested via sub index: 0 and indexes according to
→ table 65.
Real-time data can be obtained either in IEEE floating-point or fixed-point
format. For data displayed in fixed-point format, each result is presented as a
multiplication of the real-time data with a scaling factor. Energy objects can
only be obtained in fixed-point format.
Registers for which the IEEE floating-point value is not specified are only
supported in fixed-point format (FP).
Table 65: Real-time data register - EtherCAT
Index (Hex)
IEEE
Fixed
floating
point (FP)
point
2038
20B6
2039
20B7
203A
20B8
203B
20B9
203C
20BA
203D
20BB
203E
20BC
203F
20BD
2040
20BE
2041
20BF
2042
20C0
2043
20C1
2048
20C6
2049
20C7
204A
20C8
204B
20C9
204C
20CA
2051
20CF
2052
20D0
2053
20D1
20D2
20D3
20D4
20D5
20D6
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Object
Description
(Values in brackets reflect the American
notation.)
Cause of status:
High byte = primary status
Low byte = secondary status
I
(IA)
L1
I
(IB)
L2
IL3 (IC)
I
(IG)
G
I
( IN)
N
U
(VAB)
L1-L2
U
(VBC)
L2-L3
U
(VCA)
L3-L1
U
(VAN)
L1-N
U
(VBN)
L2-N
U
(VCN)
L3-N
Active 3-phase power
Reactive 3-phase power
Apparent 3-phase power
Power factor
Frequency
Peak active power demand
Product ID
Frequency
Active energy (forward)
Active energy (reverse)
Active energy combined (= forward + reverse)
Apparent energy
Active energy (forward)
10.2 EtherCAT
Unit
Scale
factor (FP)
A
10
A
10
A
10
A
10
A
10
V
10
V
10
V
10
V
10
V
10
V
10
W
1
Var
1
VA
1
100
Hz
10
W
1
Hz
100
kWh
1
kWh
1
kWh
1
kVAh
1
Wh
1
111