Eaton PXR10 Manual page 126

Electronic trip unit power xpert release for nzm circuit breakers
Hide thumbs Also See for PXR10:
Table of Contents

Advertisement

10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
Index
Bit
Mask
[Hex]
field
field
2011
2012
0
0x0001
2013
0 - 1
0x0003
2014
0
0x0001
2015
122
Setpoint name
R/W
Settings - instan-
R/W
taneous short-
circuit release (I
)
i
Type of ground-
R
fault detection
Settings - functio-
R/W
ning of the
ground-fault
protection
ground-fault
R/W
release - wave-
form
Settings - ground-
R/W
fault release (Ig)
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Format
Description or value
Unsigned
Settings - instantaneous short-circuit release
(I
= n x I
)
i
n
NZM PXR20: R
NZM PXR25: R/W
NZM PXR20:
20: 2
30: 3
40: 4
50: 5
60: 6
70: 7
80: 8
90: 9
100: 10
110: 11
120: 12
140: 14
160: 16
180: 18
The following applies to the NZM PXR25:
The value range [20 - 180] corresponds to
2 to 18, in increments of 0.1 (1 for values)
Unsigned
Type of ground-fault detection: 0 = differential
current detection
Encoded
Type of ground-fault protection
0: trip
1: alarm
2: OFF
Encoded
ground-fault release - waveform:
0: flat
2
1: I
t
Unsigned
Settings - ground-fault release (I
NZM PXR20: R
NZM PXR25: R/W
NZM PXR20:
20: 0.2
30: 0.3
40: 0.4
60: 0.6
80: 0.8
100: 1.0
100: 1000
The value range [20 - 100] corresponds to 0.2 to
1.0, in increments of 0.1 (10 for values)
Unit
A
= n x I
)
A
g
n

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pxr20Pxr25

Table of Contents