Eaton PXR10 Manual page 65

Electronic trip unit power xpert release for nzm circuit breakers
Hide thumbs Also See for PXR10:
Table of Contents

Advertisement

Register
Bit
Mask field
number
field
403000
15 – 0
0xFFFFFF
403001
15 – 0
0xFFFFFF
403002
12 – 0
0x1FFFF
403003
2 – 0
0x0007
403004
3 – 0
0x000F
403005
Table 26: Setting group 1: "protection group"
Setpoint name
Password
Group 1 = protection
Rated current
Frame size
Trip type version - part 1
Trip type version - part 2
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
9 Modbus RTU – integrated Modbus port specification
R/W
Format
Description or value
W
Encoded
0000 (default setting)
R/W
0x01FF
R
Encoded
NZM2: 25, 40, 63, 90, 100, 140, 160, 200,
220, 250, 300
NZM3: 250, 350, 400, 450, 600, 630
NZM4: 550, 600, 630, 800, 875, 1000,
1200, 1250, 1400, 1600
R
Encoded
The frame size indicates the breaker
type.
11: NZM2
12: NZM3
13: NZM4
R
Encoded
Bit 0: LdSel: with overload protection
I
r
Bit 1: SdSel: with short-time delayed
short-circuit protection I
Bit 2: InstSel: with instantaneous short-
circuit release I
Bit 3: GfSel: with ground-fault protection
I
g
Bit 4: ARMSel: with maintenance mode =
1
Bit 5: OvrideSel: with instantaneous
release function = 1
Bit 6: not used
Bit 7: MotorSel: with motor-protection
function = 1
Bit 8: NeuSenorSel: 4-pole device = 1
3-pole device = 0
Bit 9: ThermalSel: with thermal memory =
1
Bit 12: VoltSel: with voltage meter = 1
Bit 13:
0: PXR20
1: PXR25
R
Encoded
Bit 0: ModbusSel: with integrated
Modbus RTU = 1
Bit 1: CAMSel: with CAM RS422 = 1
Bit 2: IOModuleSel: with IO module = 1
Bit 3: RelaySel: with relay module = 1
Bit 4: ZSISel: with zone selectivity = 1
Bit 12: NZM_ACB_Sel:
degree of protection
0: IZMX
1: NZM
Bit 13: IECSel:
0: UL
1: Standard IEC
9.3 Modbus register map
= 1
= 1
sd
= 1
i
= 1
Unit