Project configuration
5.13.4

Dynamic muting

When Activate muting is selected for one of the inputs 3, 9, 10 or 11, muting can be activ-
ated and deactivated dynamically.
}
Conditions for the occurrence of muting
– One of the inputs 3, 9, 10 or 11 is connected to a controller and it receives a high sig-
– When configuring the inputs, Activate muting is configured for this input in
– The first sensor has detected a conveyed material and the second sensor also detec-
5.14

Override

The override function can be used for the three types according to the timing diagrams.
}
Single-channel pulses
}
Activation by rising edge
}
Activation by rising signal (only when using the 12-pin connection)
Protective zone
Single-channel
Fig.: Timing diagram for override function single-channel pulses
Operating Manual PSEN sc L 3/5 series
1005056-EN-01
If material is transported from the left-hand side, the cycle is re-
versed. The output side becomes the input side and the flow
starts with the second muting sensor on the output side.
nal from there when muting is to be activated
PSENscan Configurator
ted it max. 4 s later or the first sensor and the second sensor detected conveyed ma-
terial simultaneously
On
Off
On
Status
Override
Off
24 V
Pulse
0 V
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
t
2 s