Appendix 1 Differences And Compatibility With The Fr-F840; Fr-F840 - Mitsubishi Electric FR-F806-E Hardware Instruction Manual

Inverter for fans and pumps, ip55/ul type 12
Table of Contents

Advertisement

Appendix 1
Item
Protective structure
Multiple rating
(Pr.570 Multiple rating
setting)
Internal fan
Protective function
Pr.30 Regenerative
function selection
Pr.71 Applied motor
Pr.255 Life alarm status
display
Pr.998 PM parameter
initialization
DC reactor
Operation panel
118
APPENDIX
Differences and compatibility
with the FR-F840

FR-F840

Enclose type (IP20): FR-F840-00620(30K) or
lower
Open type (IP00): FR-F840-00770(37K) or higher
SLD, LD (initial setting) rating
(Setting range "0, 1")
None
Setting range "0 to 2, 10, 11, 20, 21, 100 to 102,
110, 111, 120, 121"
Setting range "0 to 6, 13 to 16, 20, 23, 24, 40, 43,
44, 50, 53, 54, 70, 73, 74, 210, 213, 214, 240, 243,
244, 8090, 8093, 8094, 9090, 9093, 9094"
Setting range (reading only) "0 to 15"
Setting range "0, 12, 14, 112, 114, 8009, 8109,
9009, 9109"
Option
FR-DU08
• Display type: LED
• Operation mode switching key:
PU/EXT key
• Protective structure: IP40 (except for the PU
connector section)
FR-F846-L2
Dust- and water-proof type (IP55): all capacities
Not applicable(LD rating equivalent)
(None (setting unavailable))
Provided
Internal-circulation fan alarm (FN2), Abnormal
internal temperature (E.IAH) provided
Setting range "0, 2, 10, 20, 100, 102, 110, 120"
Setting range "0 to 6, 13 to 16, 20, 23, 24, 40, 43,
44, 50, 53, 54, 70, 73, 74, 8090, 8093, 8094, 9090,
9093, 9094"
Setting range (reading only) "0 to 31"
Setting range "0, 8009, 8109, 9009, 9109"
Built-in
FR-LU08-01
• Display type: LCD
• Operation mode switching key:
HAND/AUTO key
• Protective structure: IP55 (except for the PU
connector section)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents