Mitsubishi Electric FR-F806-E Hardware Instruction Manual page 68

Inverter for fans and pumps, ip55/ul type 12
Table of Contents

Advertisement

• Harmonic content (Values of the fundamental current is 100%)
Reactor
Used (DC side)
30
Used (AC, DC sides)
28
• Calculation of equivalent capacity P0 of harmonic generating equipment
"Equivalent capacity" is the capacity of a 6-pulse converter converted from the capacity of consumer's harmonic generating
equipment and is calculated by the following equation: If the sum of equivalent capacities is higher than the limit (Refer to
page
66), harmonics must be calculated with the following procedure:
P0 = ∑ (Ki  Pi) [kVA]
Ki: Conversion coefficient (Refer to
Pi: Rated capacity of harmonic generating equipment
i: Number indicating the conversion circuit type
• Calculation of outgoing harmonic current
Outgoing harmonic current = fundamental wave current (value converted from received power voltage)  operation ratio 
harmonic content
• Operation ratio: Operation ratio = actual load factor  operation time ratio during 30 minutes
• Harmonic content: Refer to
• Rated capacities and outgoing harmonic currents of inverter-driven motors
Fundamental
wave current
Applicable
(A)
motor (kW)
400 V
0.4
0.81
0.75
1.37
1.5
2.75
2.2
3.96
3.7
6.50
5.5
9.55
7.5
12.8
11
18.5
15
24.9
18.5
30.7
22
36.6
30
49.0
37
60.4
45
73.5
55
89.9
75
123
90
147
110
179
132
216
160
258
220
355
250
403
280
450
315
506
355
571
400
643
450
723
500
804
560
900
630
1013
5th
7th
11th
13
8.4
9.1
7.2
page
66)
page
67.
Fundamental
wave current
Rated
converted
capacity
from 6.6 kV
(kVA)
(mA)
49
0.57
83
0.97
167
1.95
240
2.81
394
4.61
579
6.77
776
9.07
1121
13.1
1509
17.6
1860
21.8
2220
25.9
2970
34.7
3660
42.8
4450
52.1
5450
63.7
7455
87.2
8909
104
10848
127
13091
153
15636
183
21515
252
24424
286
27273
319
30667
359
34606
405
38970
456
43818
512
48727
570
54545
638
61394
718
PRECAUTIONS FOR USE OF THE INVERTER
13th
17th
5.0
4.7
3.2
4.1
3.2
2.4

Rated capacity: Determined by the capacity of the
applied motor and found in Table 5. The rated
capacity used here is used to calculate the generated
[kVA]

harmonic amount and is different from the power
supply capacity required for actual inverter drive.
Outgoing harmonic current converted from 6.6 kV (mA)
(With a DC reactor, 100% operation ratio)
5th
7th
11th
13th
14.7
6.37
4.116
2.45
24.9
10.79
6.972
4.15
50.1
21.71
14.03
8.35
72
31.20
20.16
12
118.2
51.22
33.10
19.7
173.7
75.27
48.64
28.95
232.8
100.9
65.18
38.8
336.3
145.7
94.16
56.05
452.7
196.2
126.8
75.45
558
241.8
156.2
93
666
288.6
186.5
111
891
386.1
249.5
148.5
1098
475.8
307.4
183
1335
578.5
373.8
222.5
1635
708.5
457.8
272.5
2237
969.2
626.2
372.8
2673
1158
748.4
445.5
3254
1410
911.2
542.5
3927
1702
1100
654.6
4691
2033
1313
781.8
6455
2797
1807
1076
7327
3175
2052
1221
8182
3545
2291
1364
9200
3987
2576
1533
10382
4499
2907
1730
11691
5066
3273
1949
13145
5696
3681
2191
14618
6335
4093
2436
16363
7091
4582
2727
18418
7981
5157
3070
Power supply harmonics
19th
23rd
25th
3.0
2.2
1.6
1.4
17th
19th
23rd
2.303
1.568
1.47
3.901
2.656
2.49
7.849
5.344
5.01
11.28
7.68
7.2
18.52
12.61
11.82
27.21
18.53
17.37
36.47
24.83
23.28
52.69
35.87
33.63
70.92
48.29
45.27
87.42
59.52
55.8
104.3
71.04
66.6
139.6
95.04
89.1
172
117.1
109.8
209.2
142.4
133.5
256.2
174.4
163.5
350.4
238.6
223.7
418.7
285.1
267.3
509.9
347.1
325.4
615.3
418.9
392.7
734.9
500.4
469.1
1011
688.5
645.5
1148
781.6
732.7
1282
872.7
818.2
1441
981.3
920
1627
1107
1038
1832
1247
1169
2059
1402
1315
2290
1559
1462
2564
1745
1636
2886
1965
1842
25th
1.078
1.826
3.674
5.28
8.67
12.74
17.07
24.66
33.2
40.92
48.84
65.34
80.52
97.9
119.9
164
196
238.7
3
288
344
473.3
537.3
600
674.7
761.3
857.3
964
1072
1200
1351
67

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents