Display Functions; User Settings - Eaton 5PX 1000 RT2U Installation And User Manual

Table of Contents

Advertisement

2.5 Display functions

Press the Enter (
through the menu structure. Press the Enter (
or return to the previous menu.
Menu map for Display Functions.
Main menu
Measurements
Control
Settings
Fault log
Identification

2.6 User settings

The following table displays the options that can be changed by the user.
Local settings
In/Out settings
614-03797-00_EN
) button to activate the menu options. Use the two middle buttons (
Submenu
Display information or Menu function
Load W VA / Load A pf / Output V Hz / Input V Hz /
Battery V min / Efficiency / Power usage
Load Segments
Group 1: ON / OFF
Group 2: ON / OFF
These commands overrule user settings for load segments.
Start battery test
Starts a manual battery test
Reset fault state
Clears active fault (UPS restart required)
Restore factory settings Returns all settings to original values
Reset power usage
Clears power usage measurements
Local settings
Sets product general parameters
Input / output settings
Sets Input and output parameters
ON / OFF settings
Sets ON / OFF conditions
Battery settings
Sets battery configuration
Displays event log or alarms
UPS Type / Part Number / Serial Number / Firmware release /
Com card address
Description
Available settings
Language
[English] [French] [German] [Italian]
[Portuguese] [Spanish] [Russian]
Menus, status, notices and alarms,
UPS fault, Event Log data and
settings are in all supported lan-
guages.
LCD settings
Authorizes to modify LCD screen
brightness and contrast to be
adapted to room light conditions.
Audible alarm
[Yes] [No]
Authorizes to enable or disable
the buzzer if an alarm occurs.
Output voltage
Low voltage: [100 V] [120 V] [125 V]
High voltage: [200 V] [208 V] [220 V]
Input thresholds
[Normal mode] [Extended mode]
Extended mode authorizes lower
input voltage (70 V) without
transferring to battery.
This can be used if the load can
withstand low voltage supply.
Sensitivity
[High] [Low]
High: for sensitive equipment,
UPS will easily transfer to battery
when utility conditions are becoming
bad.
Low: for equipment that can
withstand bad utility conditions,
in that case, the UPS will not transfer
to battery.
Load segments -
[No Delay] [1 s] [2 s]...[65354 s]
Auto start delay
The equipment are powered on
with the specified delay relative
to the primary group.
) button to select an option. Press the
[230 V] [240 V]
2. Presentation
and
) to scroll
button to cancel
Default settings
English
User selectable when UPS is
powered for the first time.
Yes
Low Voltage model: 110 V,
High Voltage model: 230 V,
User selectable when UPS is
powered for the first time.
Normal mode
High
Group 1: 3 s
Group 2: 6 s
Page 11